RMS-SNMP01A SNMP Card
User Manual
3 Installation and Basic Settings
Issue 08 (2020-01-09)
Copyright © Huawei Technologies Co., Ltd.
19
(7) Reset button
(8) Dual in-line package
(DIP) switch
(9) Fastener
The external dry contact card connects to the UPS over an SNMP card.
how to connect cables to the external dry contact card.
The RMS-SNMP01A card does not support connection to a temperature and humidity sensor
and an external dry contact card at the same time.
Figure 3-14
Connecting cables to the external dry contact card
Refer to the external dry contact card user manual and set the card address to 8.
shows the
DIP switch status of the RMS-RELAY02B. 1 is set to ON and other toggle switches are set to OFF. The
baud rate is set to
9600
.
Figure 3-15
DIP switch