7.1.22 Correlation Relationship of Parameters
When setting parameters, pay attention to the following relationships.
Alarm Parameters
Power underfrequency alarm threshold < Power overfrequency alarm threshold
Backup power underfrequency alarm threshold < Backup power overfrequency alarm
threshold
Supply air high temperature alarm thr 5°C ≤ Return air high temperature alarm
threshold
Supply air high temperature alarm thr 5°C ≤ Hot aisle high temperature alarm
threshold
Cold aisle high temperature alarm thr 5°C ≤ Hot aisle high temperature alarm
threshold
Cold aisle high temperature alarm thr 5°C ≤ Return air high temperature alarm
threshold
Supply air low temperature alarm thr 5°C ≤ Return air low temperature alarm
threshold
Supply air low temperature alarm thr 5°C ≤ Hot aisle low temperature alarm
threshold
Cold aisle low temperature alarm thr 5°C ≤ Hot aisle low temperature alarm
threshold
Cold aisle low temperature alarm thr 5°C ≤ Return air low temperature alarm
threshold
Parameters of Teamwork Settings
Number of smart cooling products in this group ≥ Number of running smart cooling products
in this group
Parameters of Cooling cap. mgt.
Upper limit of water supply temperature > Lower limit of water supply temperature
Parameters of Indoor fan
Min indoor fan speed ≤ Min indoor fan speed in silent mode ≤ Medium indoor fan speed
in silent mode ≤ Max indoor fan speed in silent mode ≤ Max indoor fan speed
Min return/supply air temp difference in silent mode ≤ Medium return/supply air temp
difference in silent mode ≤ Max return/supply air temp difference in silent mode
Min indoor fan speed ≤ Min speed for heating ≤ Max indoor fan speed
Min indoor fan speed ≤ Min speed for humidifying ≤ Max indoor fan speed
Min indoor fan speed ≤ Max speed for dehumidifying ≤ Max indoor fan speed
Min indoor fan speed ≤ Min fresh air speed ≤ Max indoor fan speed