Figure 3-47 Connecting power cables (NetCol5000-C030/C032)
1. Remove screws from both ends of the clip to remove it.
2. Connect the cables with crimped terminals to the L, N, and PE.
NO TE
NetCol5000-C065 uses a common screwdriver to secure the cables, NetCol5000-C030/
C032 uses a 100-120 mm screwdriver to secure the cables.
3. Place the connected power cables vertically, use the clip to secure them in a
proper position, and use screws to secure the clip.
4. Fasten the power cable to the vertical pillar by cable ties every 150 mm to
200 mm.
Step 4 Use a multimeter to check for a short circuit between L and N of AC1 and AC2.
Use a multimeter to check for a short circuit between L, N, and PE.
●
If there is a short circuit, remove the cable and reconnect it using the method
. After verifying the connection, perform
●
If there is no short circuit, perform
Step 5 Check that the cable connections are secure.
●
If the cable connections are loose, fasten the connections.
●
If the cable connections are secure, the connection is complete.
Step 6 Reinstall the cover of the electric control box.
----End
3.12.4 Teamwork Networking and Monitoring
3.12.4.1 Main Control Board Ports
NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual (2019)
3 Installation
Issue 03 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
66