Pipes have been properly connected.
Procedure
Step 1 Manually turn the chilled water valve to the maximum (100%), as shown in
.
Step 2 Connect a reducing valve, pressure gauge, and nitrogen cylinder to any needle
valve of the smart cooling product, as shown in
0.8 MPa nitrogen (the pressure should reach 0.8 MPa after it is stabilized), and
keep it for 24 hours.
Figure 3-37 Injecting nitrogen (NetCol5000-C065)
Figure 3-38 Injecting nitrogen (NetCol5000-C030/C032)
Step 3 After 24 hours, if the pressure drop is less than 0.01 MPa, the pipes do not leak.
Open the exhaust valve using a screwdriver, and close the valve when there is no
airflow through the valve. Then you can perform the following operations.
NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual (2019)
3 Installation
Issue 03 (2020-08-30)