NetCol5000-A021 In-row Air Cooled Smart Cooling
Product
User Manual (208 V)
3 Installation Guide
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
30
The object shown in the dotted line box is the water inlet pipe connector with inner screw threads
delivered with smart cooling products. The hose clamp as shown by (5) in the preceding figure is
provided in standard configuration. Other parts are not provided and need to be purchased.
3.1.2.5 Drainpipe
A drainpipe should be able to withstand a temperature greater than 85°C. Otherwise, pipe
deformation may occur (for equipment configured with a humidifier).
A drainpipe can be connected in two ways:
Top pipe routing: For the connection method of the water pump drainpipe, see method A
in
Bottom pipe routing: See methods B and C in
Determine a pipe connection method based on site pipe materials.
Figure 3-4
Connecting a drainpipe
(1) Rigid pipe: 1/2-inch BSPT, external thread, made of PP-R,
C-PVC, or other materials
(2) Hose clamp
(3) Hose: inner diameter of 14 mm, made of EPDM or other
materials
(4) Hose delivered
with the fittings
(5) Rigid pipe conversion adapter: 5/8-inch outer diameter,
adapting for 1/2-inch BSPP internal thread connection
Components inside the dashed-line boxes are ports on the equipment. Components 2, 4, and 5 are
mandatory. Other components are subject to engineering procurement.