NetCol5000-A021 In-row Air Cooled Smart Cooling
Product
User Manual (208 V)
2 Product Description
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
21
Item
Specifications
Water supply
Water supply pressure range: 0.1 MPa to 0.7 MPa.
Water supply temperature range: 1°C to 40°C.
Water quality must meet requirements specified in
Drainage
Drainpipes can withstand high temperature ≥ 85°C, (for units
that are configured with a humidifier).
Power supply
Ground fault circuit interrupters are not recommended to be
used on main circuit. If ground fault circuit interrupters are
required by the customer or according to local regulations, use
the residual current circuit breaker (RCCB) that is not sensitive
to the single–phase DC pulse and transient current pulse.
Note: If some conditions are not met, please contact Huawei technical support.
Water Quality Requirements
If the inlet water contains large granules, install a water filtering device at the inlet port to
prevent pipe blockage.
Table 2-6
Water quality requirements
Item
Requirement
Unit
Hydrogen ion
7 to 8.5
pH
Conductivity at 20°C
(σ
20
)
a
125 to 1250
µS/cm
Inlet water hardness
specifications
b
≤ 100
mg/L
a: When σ
20
is less than 125 µS/cm, the first vapor exhausting duration of the humidifier is
long; when σ
20
greater than 1250 µS/cm, the humidifier service life is affected.
b: A water softener needs to be installed if the inlet water hardness exceeds 100mg/L
(CaCO
3
).
2.6 Technical Specifications