4 ACC Introduction
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
93
successfully started or shut, the system displays a message, indicating that the command is
successfully triggered.
Figure 4-5
Start and shutdown
If a power failure occurs and the smart cooling product is powered on again, the smart cooling
product automatically restores to the original state (start or shutdown) before the power failure.
The hardware port for controlling the status of the
remote dry contact
or
On/Off status on remote
is reserved on the ACC. The status of the
remote dry contact
and
On/Off status on remote
is on by
default.
The operations that start the smart cooling product successfully by the LCD button or by element
management system (EMS) is effective only when the
remote dry contact
or
On/Off status on
remote
is on the status of on.
In start mode, the
Start
button is green (unavailable) and the
Shutdown
button is gray (available).
In shutdown mode, the
Shutdown
button is green (unavailable) and the
Start
button is gray
(available).
----End
4.3.2.2 Setting Temperature and Humidity Values
Procedure
Step 1
On the home screen, choose
Settings
>
System Settings
>
T/H Sensor
displayed.
Figure 4-6
Setting temperature and humidity values
Step 2
Set the parameters by referring to