4 ACC Introduction
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
94
You are not recommended to modify the parameters not listed in
Table 4-2
Parameter description
Parameter
Description
Configuration Principle
T/H control type
Sets
Cold-aisle
,
Hot-aisle
,
Return-air
, or
Supply-air
as
required. The
temperature and
humidity set points
correspond to the
selected control type
can be set.
Return-air
: For a hot aisle, select
Return-air
to control the temperature and
humidity around the air return vent of the
smart cooling product.
Supply-air
: For a cold aisle, select
Supply-air
to control the temperature and
humidity around the air supply vent of the
smart cooling product.
Cold-aisle
: For a cold aisle, select
Cold-aisle
to control the temperature and
humidity of the aisle. The temperature and
humidity values come from the humidity
and temperature sensor in the aisle.
Hot-aisle
: For a hot aisle, choose
Hot-aisle
to control the temperature and
humidity of the aisle. The temperature and
humidity values come from the humidity
and temperature sensor in the aisle.
Temp control
mode
Controls the
temperature inside the
room or aisles based
on the
Average
,
Maximum
, or
Minimum
of the
temperatures collected
by each sensor.
Average
: Select
Average
if the
temperature is to be controlled based on
the averaged data value collected by the
collector.
Maximum
: Select
Maximum
if the
temperature is to be controlled based on
the maximum data value collected by the
collector.
Minimum
: Select
Minimum
if the
temperature is to be controlled based on
the minimum data value collected by the
collector.
Supply-air temp
set point,
Supply-air humid
set point
Sets the required
humidity and
temperature in a room
or aisle.
The ACC controls the temperature and
humidity based on the set value. For example,
if
Temp control type
is set to
Return-air
,
Return-air temp set point
is set to
30.0
, and
Return-air humid set point
is set to
25.0
, the
ACC will control the temperature and
humidity around the return-air vent of the
smart cooling product to a temperature of
30°C and humidity of 25% RH.
Return-air temp
set point,
Return-air humid
set point
Cold-aisle temp
set point,
Cold-aisle humid
set point