NetCol5000-A 42 kW Air Cooled In-row Precision Air
Conditioner
User Manual
3 Installation Guide
Issue 01 (2017-07-27)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
22
The equipment room should be thermal-insulated. Moisture proof measures should be
applied to walls and floors.
Take measure to avoid damaging cabinet components and cables during cabinet
transportation.
To ensure good ventilation, check that the indoor unit is not placed in the corner of a
room or at the end of a long and narrow room.
All doors and windows of the equipment room should be closed to reduce the additional
load of the precision air conditioners during the system running.
Precautions for Connecting Refrigerant Pipes
Pipe length mentioned in this document is equivalent.
When selecting the refrigerant pipes, note the following:
Avoid elbows and ensure that the connection between the indoor and outdoor units is the
shortest.
After determining the best pipe route between the indoor and outdoor units, calculate the
number of the components that cause local resistance loss, for example, elbows, and
convert them into the equivalent length to straight pipes, as shown in
The total length of pipes connecting the indoor unit and outdoor unit (L) equals to the
equivalent straight length of elbows and connectors plus the length of the straight pipes
connecting the indoor unit and outdoor unit.
Concrete floor does not support underfloor piping.
Precautions for Connecting Cables
Connections of all power cables, control cables, and ground cables must comply with
local electrical regulations, and the cable specifications should comply with local cabling
specifications.
For details about current in full load, see the device nameplate.
Cable connections can be performed only by qualified technicians. The installation
personnel must wear insulation and protection equipment, such as protective gloves.
All precision air conditioners must be reliably grounded.
Concrete floor does not support underfloor cable routing.
3.2 Installation Preparation
To ensure the optimal operating condition and longest service life, install the NetCol5000-A
in strict accordance with requirements.
3.2.1 Tools
The following tables list the tools for installing the NetCol5000-A. Add or delete tools as
required.
Содержание NetCol5000-A
Страница 264: ...NetCol 5000 A 42 kW Air Cooled In row Precision Air Conditioner User Manual D Electrical Conceptual Diagram ...
Страница 265: ...NetCol 5000 A 42 kW Air Cooled In row Precision Air Conditioner User Manual D Electrical Conceptual Diagram ...
Страница 266: ...NetCol 5000 A 42 kW Air Cooled In row Precision Air Conditioner User Manual D Electrical Conceptual Diagram ...
Страница 267: ...NetCol 5000 A 42 kW Air Cooled In row Precision Air Conditioner User Manual D Electrical Conceptual Diagram ...