Configuration
Pipes to Be Connected
Condensate pump.
No heater or
humidifier
Condensate pump drainpipe and self-drainpipe
(optional)
NOTE
Optional: If there are raised floors or bases, connect the self-
drainpipe. Otherwise, you are not required to connect the self-
drainpipe. Condensate pump drainpipe and self-drainpipe should
not be connected together to avoid water in the self-drainpipe
flowing back to the pump.
Heater and
humidifier. No
condensate pump
Humidifier water inlet and self-drainpipe
No condensate
pump, heater or
humidifier
Self-drainpipe
The following describes how to install an self-drainpipe. For details about how to
connect humidifier water inlet pipe and water pump drainpipe, see the method of
connecting the self-drainpipe.
Procedure
Step 1 Remove plugs from the pipe, as shown by 1 in
Figure 3-29 Connecting self-drainpipe
NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width)
3 Installation Guide
Issue 17 (2020-10-22)
Copyright © Huawei Technologies Co., Ltd.