Temperature
(°C)
Saturation
Pressure-
Surface
Pressure
(MPa)
Temperatur
e (°C)
Saturatio
n
Pressure-
Surface
Pressure
(MPa)
Temperatu
re (°C)
Saturati
on
Pressur
e-
Surface
Pressur
e (MPa)
10
0.99
29
1.74
48
2.83
11
1.02
30
1.79
49
2.9
12
1.05
31
1.84
50
2.97
13
1.09
32
1.89
51
3.04
14
1.12
33
1.94
52
3.11
15
1.16
34
1.99
53
3.19
16
1.19
35
2.04
54
3.26
17
1.23
36
2.1
55
3.34
18
1.27
37
2.15
N/A
N/A
3.1.2.2 Refrigerant Oil
The recommended refrigerant oil is Danfoss 160SZ. You can purchase it from
Huawei, or purchase it by yourself after being confirmed by Huawei.
NO TE
If the low-temperature component is connected, additional refrigerant oil. If not, ignore the
refrigerant oil.
3.1.2.3 Pipe Components
Pipe components are optional and include:
●
Liquid pipe: copper pipe (for R410A) external diameter: 5/8 inch; thickness: 1.0
mm; pressure tolerance range: ≥ 4.5 MPa.
●
Gas pipe: copper pipe (for R410A) external diameter: 7/8 inch; thickness: 1.2
mm; pressure tolerance range: ≥ 4.5 MPa.
●
Thermal insulation foam: thickness ≥ 13 mm.
●
Oil traps and inverted traps: To ensure the NetCol5000-A reliability, make an
oil trap every 5 m to 6 m along pipes in the vertical direction and make an
inverted trap respectively at the intake vent and exhaust vent of the outdoor
unit.
shows the specifications for the oil traps and inverted traps.
NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width)
3 Installation Guide
Issue 17 (2020-10-22)
Copyright © Huawei Technologies Co., Ltd.
30