Figure 3-2 Oil trap and inverted traps (unit: mm)
Table 3-8 Specifications for oil traps and inverted traps
No.
Name
Copper Pipe
Outer Diameter
and Thickness
Technical Requirements
1
Oil trap
22.2 mm x 1.2
mm
The flaring inner diameter of the
copper pipe is 22.4 mm, and the
necking outer diameter is 19.5 mm.
2
Gas pipe
inverted trap
22.2 mm x 1.2
mm
The flaring inner diameters at both
ends of the copper pipe are 22.6
mm.
3
Liquid pipe
inverted trap
15.9 mm x 1.0
mm
The flaring inner diameters at both
ends of the copper pipe are 16.3
mm.
Note: After the traps are made, verify that the surface is smooth and even.
3.1.2.4 Humidifier Water Inlet Pipe, Pump Drainpipe, and Automatic
Drainpipe
NO TICE
Drainpipes must be able to withstand temperatures higher than 85°C. Otherwise,
the pipes may be deformed. This notice is for the equipment configured with a
humidifier.
describe how to install the humidifier water inlet pipe,
pump drainpipe, and automatic drainpipe.
NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width)
3 Installation Guide