Figure 6-21 Replacing the humidifier cylinder
Step 4 Loosen the belt around the humidifier cylinder and remove the cylinder, as shown
by (2) and (3) in
Step 5 Open the rubber pad on the cable port, and clear the glue on the port using a
flat-head screwdriver, as shown by (4) in
.
Step 6 Remove the screws from the electrode cable connection terminals above the
humidifier cylinder using the 10# socket wrench, remove the cable connection
terminals, and remove the cable from the high water level sensor, as shown by (5)
in
Step 7 Install a new humidifier cylinder by performing
in the reverse
order, and start the humidifier.
NO TE
When replacing the humidifier cylinder, you do not need to apply glue to the cable
connection port again.
Step 8 Power on the humidifier, choose Maint > Diagnostic mode on the main menu,
and enter 100%. The water is injected to the humidifier. Check whether the
humidifier works properly. If yes, exit the diagnostic mode.
NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width)
6 System Operation and Maintenance
Issue 17 (2020-10-22)
Copyright © Huawei Technologies Co., Ltd.
221