NO TE
Ensure that all water bump pipe joints are sealed with sealant.
Step 8 Power on the condensate pump and test it referring to
. Ensure that the condensate pump works properly and no water leaks.
Step 9 Tap Maint > Performance Maint to clear the condensate pump total runtime.
----End
6.5.7 Replacing Humidifier Cylinder
Prerequisites
●
Recommended tools: flat-head screwdriver and 10# socket wrench.
●
The humidifier cylinder needs to be replaced.
●
A spare and functional humidifier cylinder is available.
Context
The rear door is opened for rear-access maintenance.
CA UTION
After the equipment is powered off, wait for a period and replace the humidifier
tank until the pipeline temperature is approximate to the room temperature to
avoid scald.
Procedure
Step 1 Press down the drainage button to ″I″ on one side of the electrical control box to
drain the water out of the humidifier cylinder.
Step 2 Tap Shutdown on the main menu. Open the rear door and remove the air filters.
Switch off the main circuit breaker QF1 and the front end circuit breaker.
NO TICE
Exercise cautions when performing operations on the screen because the
equipment is under power.
Step 3 Loosen the hose clamp above the humidifier cylinder using the flat-head
screwdriver, and remove the vapor hose from the humidifier cylinder, as shown by
.
NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width)
6 System Operation and Maintenance
Issue 17 (2020-10-22)
Copyright © Huawei Technologies Co., Ltd.