NO TICE
For safe system operation, when smart cooling product components are started,
the following coupling relationships are presented:
● When the compressor (including fixed frequency and frequency-converting) is
started, the indoor fans, outdoor fans, and the liquid solenoid valve
automatically start.
● When the electric heater is started, the corresponding indoor fan automatically
starts.
● When the electrode humidifier is started, the corresponding indoor fan
automatically starts.
● When the infrared humidifier is started, the corresponding indoor fan and
water supply valve automatically start.
●
If you need to manually turn on or off system components in diagnostic
mode, log in as the Admin or Engineer user. Ensure that the smart cooling
product is started before operation.
●
For details about the parameters and specifications to be set, see the
commissioning chapter in the user manual of each smart cooling product.
●
This chapter describes how to commission smart cooling product components,
using the electric heater as an example.
Procedure
Step 1 Enter diagnostic mode.
Step 2 Tap On for Electric heater, as shown in
Figure 4-17 Starting up the electric heater
After the electric heater is started, the Off following the Electric heater turns into
On.
----End
4.6 Maintenance Guide
NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width)
4 ACC Introduction
Issue 17 (2020-10-22)