CA UTION
● When a solar inverter is faulty, try to avoid standing in front of the solar
inverter.
● Do not operate the DC switch on the solar inverter before you finish
to
● If the AC switch between the solar inverter and the power grid has
automatically disconnected, do not turn on the switch before the fault is
rectified.
● Before power-off for troubleshooting, do not touch the energized components
of the solar inverter. Otherwise, electric shocks or arcing may occur.
Procedure
Step 1
Wear proper personal protective equipment (PPE).
Step 2
If the solar inverter is not shut down due to a fault, send a shutdown command
on the SUN2000 app, SmartLogger, or management system. If the solar inverter
has shut down due to a fault, go to the next step.
Step 3
Turn off the AC switch between the solar inverter and the power grid.
Step 4
Measure the DC current of each PV input string using a clamp meter that is set to
the DC position.
●
If the current is less than or equal to 0.5 A, go to the next step.
●
If the current is higher than 0.5 A, wait until the solar irradiance decreases
and the PV string current decreases below 0.5 A at night, and then go to the
next step.
Step 5
Open the maintenance compartment door, install a support bar, and use a
multimeter to measure the voltage between the AC terminal block and the
ground. Ensure that the AC side of the solar inverter is disconnected.
Step 6
Turn off all DC input switches of the solar inverter.
Figure 8-1
Power-off for maintenance
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
8 Maintenance
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
83