Item
Description
Pin 2
DM
Pin 3
DP
Pin 4
GND
Indicators
Table 4-28 Indicators on the ECC800-Pro main control module
Indica
tor
Color
Item
Status
Description
RUN
Green
Running status
indicator
Steady on
The power supply is normal,
the program is being loaded.
Off
The power supply is
abnormal.
Blinking at
long
intervals
The software runs properly
(the indicator blinks at 0.5
Hz, on for 1s and then off
for 1s) or the ECC800-Pro
registers with the NetEco
successfully.
Blinking at
short
intervals
The ECC800-Pro does not
register with the NetEco
(the indicator blinks at 5 Hz,
on for 0.125s and then off
for 0.125s).
ALM
Red
Alarm indicator
Steady on
A system failure alarm is
generated.
Off
The system is normal.
RF_Z
Green
Communication
status indicator
Blinking at
long
intervals
A network is set up, and no
node access is allowed (the
indicator blinks at 0.5 Hz, on
for 1s and then off for 1s).
Blinking at
super
short
intervals
A network is set up, and
node access is allowed (the
indicator blinks at 10 Hz, on
for 0.05s and then off for
0.05s).
FusionPower6000
Product Description
4 Product Overview
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
46