Figure 5-30
Removing a humidifier pump
Step 7
Install the new humidifier pump by performing the preceding steps in reverse order, connect
the hoses, and install hose clamps.
Step 8
Clear up the humidifier pump total runtime.
Method 1: Log in to the ECC800 mobile phone or pad app as admin.
a.
Choose
Home
.
b.
Tap the cabinet that houses the air conditioner in the micro-module view.
c.
Tap the air conditioner to be set in the cabinet layout diagram.
d.
Choose
Real-time Data
>
Perf Maint
, clear up the humidifier pump total running
time.
Method 2: Log in to the ECC800 WebUI as admin. Choose
Monitoring
>
Air
Conditioner
>
NetCol5000-A0104
>
Controls
>
Performance Maint Ctrl
, clear up the
humidifier pump total running time.
----End