FusionModule800 Smart Small Data Center
Maintenance Guide
3 Alarm References
Issue 02 (2016-11-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
14
Component
Alarm Name
Alarm
Severity
Possible
Cause
Measures
Full water
Critical
1.
The cables
to the high
liquid level
detector are
not
connected
properly.
2.
The high
liquid level
detector is
faulty.
3.
If a
condensate
pump is
configured,
the
condensate
pump may
be faulty, or
the
condensate
pump
draining
capacity
declines.
4.
If a
condensate
pump is
configured,
the
condensate
pump
drainpipe
may be
blocked.
5.
If no
condensate
pump is
configured,
maybe the
automatic
drainage
port is
blocked, an
internal
drainpipe is
blocked, or
a drainpipe
is frozen.
1.
Check the
cables to the
high liquid
level
detector.
2.
Maintain or
replace the
high liquid
level
detector.
3.
Maintain or
replace the
condensate
pump.
4.
Clear the
obstacles in
the
condensate
pump.
5.
Clear the
foreign
matter at the
automatic
drainage
port or in
the internal
drainpipe.