Context
A T/H sensor is installed on the cabinet door frame post 1.8 m above the ground, as
shown in
If the air conditioner implements cold-aisle control, install the temperature and humidity
sensor on the door frame of the IT cabinet front door. If the air conditioner implements
hot-aisle control, install the temperature and humidity sensor on the door frame of the IT
cabinet rear door.
Procedure
Step 1
Use two M5x10 tapping screws to secure the T/H sensor base to the IT cabinet door frame 1.8
m above the ground.
Step 2
Mount the T/H sensor onto the base.
Figure 9-66
Installing a T/H sensor
----End