"ODF-G01-01-01-R" indicates that the local end of the optical fiber is connected to the
optical receiving terminal in row 01, column 01 of the ODF in row G, column 01 in the
machine room.
l
"A01-01-05-01-R" indicates that the opposite end of the optical fiber is connected to
optical receiving interface 1 in slot 05, chassis 01 in the cabinet in row A, column 01 in
the machine room.
5.4.3 Engineering Labels for Network Cables
Applicable Ranges
The labels can be applied to Ethernet cables.
Label Content
shows the information on both sides of the labels affixed to Ethernet cables.
You can also decide the label content based on the actual environment. If the device is not
installed in the cabinet, for example, you can remove the cabinet number.
Table 5-24
Information on the Ethernet cables
Content
Meaning
Example
MN-B-C-D
MN: cabinet
number
For example, A01 is the first cabinet in row A.
B: chassis
number
Numbered in bottom-up order with two digits, for
example, 01.
C: physical slot
number
Numbered with two digits in top-down and left-
right order. For example, 01.
D: network port
number
Numbered in top-down and left-right orders. For
example, 01.
MN-Z
MN: cabinet
number
For example, B02 is the second cabinet in row B.
Z: Location
number
Fill in the location number of the terminal device
on site. If the cable is connected to a device in a
cabinet, specify the serial numbers of the cabinet,
the chassis, and the Ethernet interface of the device.
For example, B02-03-12. If the cable is connected
to the Network Management Station (NMS),
specify the specific location of the NMS.
The contents of the labels for network cables connecting hubs and devices or agents and the
network cables for other purposes should be specified according to actual connections. The
details are as follows: