23
malfunction
D
Return
gas
temp.
sensor
detect range
-9 ~ 99°C
Actual testing value. Error code P4
will be shown in case of a
malfunction
E
Ambient
temp.
sensor
detect range
-9 ~ 99°C
Actual testing value. Error code P5
will be shown in case of a
malfunction
F
Electronic expansion valve step 10 ~ 47 step
N*10 step
H
Temp of solar thermal collector
0-140
℃
Measured value
,
if failure
,
show P6
Malfunctioning of the unit and error codes
When an error occurs or the protection mode is set automatically, the circuit board and the wired
controller will both display the error message.
Protection/
Malfunction
Error
code
LED
indicator
Possible reasons
Corrective actions
Standby
Dark
Normal
running
Bright
Lower
tank
water temp.
sensor failure
P1
☆
●
(1flash
1
dark)
1) The sensor open
circuit
2) The sensor short
circuit
3)PCB board failure
1) Check the sensor
connection
2) Replace the sensor
3)change the PCB board
Upper
tank
water temp.
sensor failure
P2
☆☆
●
(2 flashes 1
dark)
1) The sensor open
circuit
2) The sensor short
circuit
3) PCB board failure
1) Check the sensor
connection
2) Replace the sensor
3) change the PCB board
Evaporator
coil
temp.
sensor failure
P3
☆☆☆
●
(3 flashes 1
dark)
1) The sensor open
circuit
2) The sensor short
circuit
3) PCB board failure
1) Check the sensor
connection
2) Replace the sensor
3) change the PCB board
Return
air
temp sensor
failure
P4
☆☆☆☆
●
(4 flashes 1
dark)
1) The sensor open
circuit
2) The sensor short
circuit
3) PCB board failure
1) Check the sensor
connection
2) Replace the sensor
3) change the PCB board
Ambient
P5
☆☆☆☆☆
1) The sensor open
1) Check the sensor