background image

lp-441 Rev. 002 Rel. 008 Date 8.23.18

9

When drawing combustion air from the outside into the 

mechanical room, care must be taken to provide adequate freeze 

protection.

Failure to provide an adequate supply of fresh combustion air can 

cause poisonous flue gases to enter the living space, resulting 

in severe personal injury or death. To prevent combustion air 

contamination, see Table 2.

In the Commonwealth of Massachusetts and As Required by 

State and Local Codes:

Installation of Carbon Monoxide Detectors: At the time of installation 

or replacement of the vented gas fueled appliance, the installing 

plumber or gas fitter shall observe that a hard wired carbon 

monoxide detector with an alarm and battery back-up is installed 

on the floor level where the gas appliance is installed, unless the 

appliance is located in a detached, uninhabitable structure separate 

from the dwelling, building, or structure used in whole or in part for 

residential purposes.

In addition, the installing plumber or gas fitter shall observe that a 

hard wired carbon monoxide detector with an alarm and battery 

back-up is installed on each additional level of the dwelling, 

building, or structure served by the vented gas appliance. It shall 

be the responsibility of the property owner to secure the service 

of qualified licensed professionals for the installation of hard wired 

carbon monoxide detectors.

a. In the event that the vented gas fueled appliance is installed in 

a crawl space or attic, the hard wired carbon monoxide detector 

with alarm and battery back-up shall be installed on the next 

adjacent floor level.

b. In the event that these requirements cannot be met at the time 

of completion of installation, the owner shall have a period of 

thirty (30) days to comply with the above requirements; provided, 

however, that during said thirty (30) day period, a battery operated 

carbon monoxide detector with an alarm shall be installed.

F. Carbon Monoxide Detectors

heater. If the water heater is installed in areas where indoor air is 

contaminated (see Table 2) it is imperative that the water heater be 

installed as direct vent so that all combustion air is taken directly 

from the outdoors into the water heater intake connection.

Unconfined space

 is space with volume greater than 50 cubic feet 

per 1,000 BTU/hr (4.8 cubic meters per kW) of the total input rating of 

all fuel-burning appliances installed in that space. Rooms connected 

directly to this space through openings not furnished with doors are 

considered part of the space. See Venting Section for details.

Confined space

 is space with volume less than 50 cubic feet per 

1,000 BTU/hr (4.8 cubic meters per kW) of the total input rating of all 

fuel-burning appliances installed in that space. Rooms connected 

directly to this space through openings not furnished with doors are 

considered part of the space.

When drawing combustion air from inside a conventionally 

constructed building to a confined space, such space should be 

provided with two permanent openings: one located 6” (15cm) 

below the space ceiling, the other 6” (15cm) above the space floor. 

Each opening should have a free area of one square inch per 1,000 

BTU/hr (22cm

2

/kW) of the total input of all appliances in the space, 

but not less than 100 square inches (645cm

2

).

If the confined space is within a building of tight construction, air for 

combustion must be obtained from the outdoors as outlined in the 

Venting section of this manual.

Do not attempt to vent this water heater by any means other than 

those described in this manual. Doing so will void the warranty and 

may result in severe personal injury or death.

Approved Carbon Monoxide Detectors: Each carbon monoxide 

detector as required in accordance with the above provisions shall 

comply with NFPA 70 and be ANSI/UL 2034 listed and IAS certified.

G. Prevent Combustion Air Contamination

Install intake air piping for the heater as described in the Venting 

Section, this manual. Do not terminate exhaust in locations that can 

allow contamination of intake air.

Ensure that the intake air will not contain any of the contaminants 

in Table 2. Contaminated air will damage the heater, resulting in 

possible substantial property damage, severe personal injury, or 

death. For example, do not pipe intake air near a swimming pool or 

laundry facilities. These areas always contain contaminants.

Products to Avoid

Areas Likely to Have 

Contaminants

Spray cans containing fluorocarbons

Dry cleaning / laundry areas and 

establishments

Permanent wave solutions

Swimming pools

Chlorinated waxes / cleaners

Metal fabrication plants

Chlorine-based swimming pool chem-

icals

Beauty shops

Calcium chloride used for thawing

Refrigeration repair shops

Sodium chloride used for water 

softening

Photo processing plants

Refrigerant leaks

Auto body shops

Paint or varnish removers

Plastic manufacturing plants

Hydrochloric or Muriatic acid

Furniture refinishing areas and es-

tablishments

Cements and glues

New building construction

Antistatic fabric softeners used in 

clothes dryers

Remodeling areas

Chlorine-type bleaches, laundry 

detergents, and cleaning solvents

Garages and workshops

Adhesives used to fasten building 

products

Table 2 - Products and Areas Likely to Have Contaminants

NOTE: DAMAGE TO THE HEATER CAUSED BY EXPOSURE TO 

CORROSIVE VAPORS IS NOT COVERED BY WARRANTY.

 (Refer to 

the limited warranty for complete terms and conditions.)

H. Removing a Heater from a Common Vent System

Do not install the heater into a common vent with any other 

appliance. This will cause flue gas spillage or appliance malfunction, 

resulting in possible substantial property damage, severe personal 

injury, or death.

Failure to follow all instructions can result in flue gas spillage and 

carbon monoxide emissions, causing severe personal injury or death.

When removing an existing heater, follow the steps below.

1. Seal any unused openings in the common venting system.

2. Visually inspect the venting system for proper size and horizontal 

pitch to determine if there is blockage, leakage, corrosion, or other 

deficiencies that could cause an unsafe condition.

Содержание Phoenix 7100P-124

Страница 1: ...not be held liable for typographical errors in literature NOTE TO CONSUMER PLEASE KEEP ALL INSTRUCTIONS FOR FUTURE REFERENCE 272 Duchaine Blvd New Bedford MA 02745 www htproducts com lp 441 Rev 002 R...

Страница 2: ...Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas...

Страница 3: ...mustbeinstalledbyqualifiedandlicensedpersonnel The installer should be guided by the instructions furnished with the water heater and by local codes and utility company requirements In the absence of...

Страница 4: ...the Box 6 B How the Heater Operates 6 C Optional Equipment 6 Part 3 Prepare the Water Heater 6 A Locating the Water Heater 7 B Leveling 7 C Clearances for Service Access 8 D Residential Garage and Cl...

Страница 5: ...table water ONLY Using this water heater to heat non potable fluid WILL VOID product warranty and could result in property damage personal injury or death Do not use this water heater for anything oth...

Страница 6: ...system monitors water temperature and adjusts fan speed to regulate the heater s energy output This allows the unit to deliver the required amount of heated energy and nothing more Burner Constructed...

Страница 7: ...ontrol system components must be protected from dripping water during operation and service 5 If the heater is to replace an existing heater check for and correct any existing system problems such as...

Страница 8: ...nt termination assembly Doing so could result in severe personal injury or death Do not attempt to vent this water heater by any means other than those described in this manual Doing so will void the...

Страница 9: ...space such space should be provided with two permanent openings one located 6 15cm below the space ceiling the other 6 15cm above the space floor Each opening should have a free area of one square inc...

Страница 10: ...corrosive chemicals or elements that can damage the heat exchanger Potable water is defined as drinkable water supplied from utility or well water in compliance with EPA secondary maximum contaminant...

Страница 11: ...quired by ANSI Part 4 Piping Failure to follow the instructions in this section WILL VOID the warranty and may result in property damage severe personal injury or death DO NOT pipe this water heater w...

Страница 12: ...The expansion tank must be located as shown in Applications this manual or following recognized design methods See expansion tank manufacturer s instructions for details Use a backflow preventer speci...

Страница 13: ...temperature as low as possible Feel water before bathing or showering If thermostatic valves are required use devices specifically designed for such purpose Install these devices in accordancewithins...

Страница 14: ...all equipment and detailing required by local codes In Massachusetts you must install a vacuum relief valve per 248 CMR 6 Mixing valve application is optional but recommended to help prevent scalding...

Страница 15: ...thout water will result in dry firing NOTES FOR AIR HANDLER APPLICATION 1 MASSACHUSETTS STATE PLUMBING CODE REQUIRES A DISTANCE NO GREATER THAN 50 FEET FROM THE WATER HEATER TO THE FAN COIL IN THE AIR...

Страница 16: ...state provincial and national codes for best practices to prevent condensate freezing in the exhaust vent pipe system Improper seating of vent pipe gaskets can cause eventual gasket failure and exhaus...

Страница 17: ...p terminations clear could result in property damage severe personal injury or death The exhaust and intake components installed with this water heater must be used for near water heater piping BEFORE...

Страница 18: ...t may be opened Direct Vent 1 foot 3 feet 91 cm Power Vent 4 ft below or to side of opening 1 ft above opening C Clearance to permanently closed window D Vertical clearance to ventilated soffit locate...

Страница 19: ...piping may be used on air inlet piping only 2 Remove all burrs and debris from joints and fittings 3 When using PVC or CPVC pipe all joints must be properly cleaned primed and cemented Use only cemen...

Страница 20: ...y three feet for concealed piping b At all changes of direction c On each side of a penetration through a partition wall or ceiling and d The labels shall be black lettering that i Indicates that the...

Страница 21: ...ing support brackets on vent piping the first bracket must be within 1 foot of the water heater and the balance of 4 foot intervals on the vent pipe Venting must be readily accessible for visual inspe...

Страница 22: ...IDE VIEW LP 325 PP EXHAUST AIR INTAKE F E D C EXHAUST AIR INTAKE B Figure 10 Horizontal Snorkel Venting UNBALANCED VENTING WITH TEE INTAKE AND COUPLING EXHAUST All vent pipes must be glued properly su...

Страница 23: ...Concentric Vent Kit installation manual LP 166 for further information on venting with the optional concentric vent kits Concentric venting through an existing system must run vertically through the...

Страница 24: ...idered part of the space Confined space is space with volume less than 50 cubic feet per 1 000 Btu hour 4 8 cubic meters per kW of the total input rating of all fuel burning appliances installed in th...

Страница 25: ...rom 3 2 to 4 5 Install a neutralizing filter if required by local codes Power to the optional condensate pump is continuous When the water heater is powered off the condensate pump will remain on It i...

Страница 26: ...lp 441 Rev 002 Rel 008 Date 8 23 18 26 1 2 3 4 Figure 16 Removing and Installing the Condensate Neutralizer Water Heaters Manufactured Prior to 9 27 17 ONLY...

Страница 27: ...ns are included with the outdoor sensor to correctly mount the sensor on the exterior surface of the building It is preferable to mount the sensor on the north side in an area that will not be affecte...

Страница 28: ...ing plate LP for liquefied petroleum propane gas or Nat for natural or city gas All gas connections must be approved by the local gas supplier or utility in addition to the governing authority prior t...

Страница 29: ...being installed If there are additional gas appliances on the main supply line size the supply line for the maximum total COMBINED BTU Hr draw of the appliances This will ensure the supply line is siz...

Страница 30: ...s individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of the system at pressures greater than psi 3 5 kPa 2 The water heater must be isolated fr...

Страница 31: ...t in increments of two degrees After choosing the setpoint wait five seconds The screen will return to normal operation and the setpoint will be stored 70 160 120 Outdoor Reset Curve Enabling Outdoor...

Страница 32: ...ume water heater operation 3 Putting the Water Heater in ECO Mode Press to put the water heater in ECO Mode Press to resume normal operation 4 Changing User Setpoint Press either or once to change the...

Страница 33: ...mum tank temperature for reset curve 70 160 140 P10 Warm Weather Shutdown Temperature o C o F Outdoor temperatures greater than this value return the tank target temperature to the User Setpoint 50 10...

Страница 34: ...een cleared Press at any History Mode screens to return to the upper level menu Part 10 Start Up Procedure FOR YOUR OWN SAFETY READ BEFORE OPERATING 1 This water heater does not have a pilot It is equ...

Страница 35: ...maximum of 15 minutes 8 Test Mode can be disabled by pressing Combustion Settings on All Models Fan Speed Natural Gas NG Propane LP Low Ignition High Low Ignition High Carbon Monoxide CO PPM 1 10 2 1...

Страница 36: ...result in property damage serious personal injury or death Such damages ARE NOT covered by water heater warranty Part 12 Troubleshooting A Error Code An error code may occur during installation of the...

Страница 37: ...the sensor is 40o F 122o F 2 Check the Outdoor Temperature Sensor Ensure it is properly wired and connected and that there are no breaks cuts or other visible issues with the sensor wire 3 Use an ohmm...

Страница 38: ...ault code occurs again reset the water heater and 3 When water heater attempts to fire check voltage at the gas valve connector If there is voltage but no gas pressure on the outlet side of the valve...

Страница 39: ...erve water heater operation If fault code occurs again 3 Check the Dual Temperature Sensor Ensure it is properly wired to the control and that there are no breaks cuts or other visible issues with the...

Страница 40: ...ons been installed at least one foot above exterior grade and one foot above normal snow accumulation level Is vent piping properly supported Has vent piping been checked for leaks Has the exhaust ven...

Страница 41: ...er that has not been used for a long period of time generally two weeks or more When opening a hot water faucet in a system that has been out of use for a time keep all ignition sources electrical app...

Страница 42: ...ctrode Clean Set gap at 1 4 Clean probe with plumbers cloth to remove oxides Combination Ignitor and Flame Probe Check ionization in uA i04 in the Inquiry Mode menu Record high fire and low fire Clean...

Страница 43: ...T P A D A 4 8 6 0 P 0 0 7 7 S P M A L C w E S O H E T A S N E D N O C 5 4 4 0 P 0 0 1 7 B R A B X E L A M T P N 2 1 G N I T T I F 6 2 0 0 P 0 0 7 7 2 1 T U N K C O L 7 7 7 0 P 0 0 7 7 2 1 X 2 1 R E T...

Страница 44: ...0P 004 27 CONDENSATE HOSE w CLAMPS 7700P 068 28 FITTING 1 2 NPT MALE X BARB 7100P 044 29 LOCKNUT 1 2 7700P 002 30 ADAPTER 1 2 X 1 2 7700P 077 31 FLUE TEMPERATURE SENSOR 7450P 026 32 PRESSURE SWITCH 77...

Страница 45: ...of the water heater and NOT the date of installation of the water heater F This warranty extends only to water heaters utilized in water heating applications that have been properly installed by quali...

Страница 46: ...whenever possible d A picture of the piping near the product e For gas fired products a picture of the venting including how it exits the building All claims will be reviewed by HTP within three 3 bu...

Страница 47: ...lp 441 Rev 002 Rel 008 Date 8 23 18 47 Maintenance Notes...

Страница 48: ...allation Installation Address Product Name Serial Number s Comments Installer s Code Name Installers Phone Number Signed by Installer Signed by Customer Installation Notes IMPORTANT Customer Please on...

Отзывы: