Figure 25 - Sealing the Water Heater for Sanitary Applications

Part 11 - Shutdown

A. Shutdown Procedure

If the burner is not operating, lower the set point value to 70

o

F and 

wait for the burner to shut off. Continue to wait for the combustion 

blower to stop, so all latent combustion gases are purged from the 

system. This should take a maximum of 5 minutes. After combustion 

gases are purged turn off electrical power to the water heater.

B. Vacation Procedure

If there is danger of freezing, change the set point to 70

o

F. DO NOT turn 

off electrical power. If there is no danger of freezing, follow “Shutdown 

Procedure”.

C. Failure to Operate

Should the burner fail to light, the control will perform two more 

ignition trials prior to entering a lockout state. Note that each 

subsequent ignition trial will not occur immediately. After a failed 

ignition trial, the blower must run for approximately 10 seconds to 

purge the system. Therefore, a time period of approximately 40 to 90 

seconds will expire between each ignition trial.

If the burner lights during any one of these three ignition trials, normal 

operation will resume. If the burner lights, but goes off in about 4 

seconds, check the polarity of the wiring. See electrical connection 

section of this manual.

If the burner does not light after the third ignition trial, the control 

will enter a lockout state. This lockout state indicates that a problem 

exists with the water heater, the controls, or the gas supply. Under 

such circumstances, a qualified service technician should be contacted 

immediately to properly service the water heater and correct the 

problem.

If a technician is not available, pressing the 

 button will remove 

the lockout state so additional trials for ignition can be performed.

D. Important Notice

It is extremely important that whenever work is performed on the 

plumbing system that either:

•  The water heater is powered off, or,

•  The water heater is valved off and isolated from the plumbing 

system.

Failure to take these measures could result in a dry-firing condition.

The water heater must be full of water and the system fully purged 

BEFORE powering the water heater. Performing any work in the 

plumbing system without either powering off the water heater 

or isolating the water heater through the use of shut-off valves 

could result in a condition referred to as “dry-firing”.  Dry-firing the 

water heater will damage the heat exchanger, and could result in 

property damage, serious personal injury, or death. Such damages 

ARE NOT covered by water heater warranty.

Part 12 - Troubleshooting

A. Error Code

An error code may occur during installation of the heater. This 

condition may lead to a lock out condition of the controller, which 

will need to be manually reset by pressing the 

 button.

B. Heater Error

1. When an error condition occurs the controller will display an error 

code on the display module.

2. These error codes and several suggested corrective actions are 

included in Table 20.

3.  In the case of E07 and E13 error codes, if uncorrected, the water 

heater will go into a fault condition as described in section C. 

Lockout.

C. Lockout

1. When an fault condition occurs, the controller will display a  fault 

code (example: F00 on the display module).

2. Note the fault code and refer to Table 21 for an explanation of the 

fault code along with several suggestions for corrective actions.

3. Press the 

 button to clear the fault and resume operation. Be 

sure to observe the operation of the unit to prevent a recurrence of 

the fault. NOTE: You are allowed up to 5 “resets” to clear fault or error 

codes. After that, the controller will enter an E13 lockout state.

When servicing or replacing any components of this water heater 

be certain that:

•  The gas is off.

•  All electrical power is disconnected.

In addition, when servicing or replacing components of this water 

heater in direct contact with heater water:

•  There is no pressure in the heater. Pull the release on the 

relief valve to relieve pressure in the heater.

•  Heater water is not hot.

Failure to follow these precautions could result in property 

damage, serious personal injury, or death. Such damages ARE NOT 

covered by water heater warranty.

DO NOT USE THIS APPLIANCE IF ANY PART HAS BEEN 

SUBMERGED IN WATER.

 Immediately call a qualified service 

technician. The appliance MUST BE replaced if it has been 

submerged. Attempting to operate an appliance that has been 

submerged could create numerous harmful conditions, such as 

a potential gas leakage causing a fire and/or explosion, or the 

release of mold, bacteria, or other harmful particulates into the 

air. Operating a previously submerged appliance could result in 

property damage, severe personal injury, or death.

NOTE: 

Appliance damage due to flood or submersion is considered 

an Act of God, and IS NOT covered under product warranty.

Allowing the heater to operate with a dirty combustion chamber will 

hurt operation. Failure to clean the heat exchanger as needed by the 

installation location could result in heater failure, property damage, 

personal injury, or death. Such product failures ARE NOT covered 

under warranty.

Содержание Phoenix 7100P-124

Страница 1: ...not be held liable for typographical errors in literature NOTE TO CONSUMER PLEASE KEEP ALL INSTRUCTIONS FOR FUTURE REFERENCE 272 Duchaine Blvd New Bedford MA 02745 www htproducts com lp 441 Rev 002 R...

Страница 2: ...Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas...

Страница 3: ...mustbeinstalledbyqualifiedandlicensedpersonnel The installer should be guided by the instructions furnished with the water heater and by local codes and utility company requirements In the absence of...

Страница 4: ...the Box 6 B How the Heater Operates 6 C Optional Equipment 6 Part 3 Prepare the Water Heater 6 A Locating the Water Heater 7 B Leveling 7 C Clearances for Service Access 8 D Residential Garage and Cl...

Страница 5: ...table water ONLY Using this water heater to heat non potable fluid WILL VOID product warranty and could result in property damage personal injury or death Do not use this water heater for anything oth...

Страница 6: ...system monitors water temperature and adjusts fan speed to regulate the heater s energy output This allows the unit to deliver the required amount of heated energy and nothing more Burner Constructed...

Страница 7: ...ontrol system components must be protected from dripping water during operation and service 5 If the heater is to replace an existing heater check for and correct any existing system problems such as...

Страница 8: ...nt termination assembly Doing so could result in severe personal injury or death Do not attempt to vent this water heater by any means other than those described in this manual Doing so will void the...

Страница 9: ...space such space should be provided with two permanent openings one located 6 15cm below the space ceiling the other 6 15cm above the space floor Each opening should have a free area of one square inc...

Страница 10: ...corrosive chemicals or elements that can damage the heat exchanger Potable water is defined as drinkable water supplied from utility or well water in compliance with EPA secondary maximum contaminant...

Страница 11: ...quired by ANSI Part 4 Piping Failure to follow the instructions in this section WILL VOID the warranty and may result in property damage severe personal injury or death DO NOT pipe this water heater w...

Страница 12: ...The expansion tank must be located as shown in Applications this manual or following recognized design methods See expansion tank manufacturer s instructions for details Use a backflow preventer speci...

Страница 13: ...temperature as low as possible Feel water before bathing or showering If thermostatic valves are required use devices specifically designed for such purpose Install these devices in accordancewithins...

Страница 14: ...all equipment and detailing required by local codes In Massachusetts you must install a vacuum relief valve per 248 CMR 6 Mixing valve application is optional but recommended to help prevent scalding...

Страница 15: ...thout water will result in dry firing NOTES FOR AIR HANDLER APPLICATION 1 MASSACHUSETTS STATE PLUMBING CODE REQUIRES A DISTANCE NO GREATER THAN 50 FEET FROM THE WATER HEATER TO THE FAN COIL IN THE AIR...

Страница 16: ...state provincial and national codes for best practices to prevent condensate freezing in the exhaust vent pipe system Improper seating of vent pipe gaskets can cause eventual gasket failure and exhaus...

Страница 17: ...p terminations clear could result in property damage severe personal injury or death The exhaust and intake components installed with this water heater must be used for near water heater piping BEFORE...

Страница 18: ...t may be opened Direct Vent 1 foot 3 feet 91 cm Power Vent 4 ft below or to side of opening 1 ft above opening C Clearance to permanently closed window D Vertical clearance to ventilated soffit locate...

Страница 19: ...piping may be used on air inlet piping only 2 Remove all burrs and debris from joints and fittings 3 When using PVC or CPVC pipe all joints must be properly cleaned primed and cemented Use only cemen...

Страница 20: ...y three feet for concealed piping b At all changes of direction c On each side of a penetration through a partition wall or ceiling and d The labels shall be black lettering that i Indicates that the...

Страница 21: ...ing support brackets on vent piping the first bracket must be within 1 foot of the water heater and the balance of 4 foot intervals on the vent pipe Venting must be readily accessible for visual inspe...

Страница 22: ...IDE VIEW LP 325 PP EXHAUST AIR INTAKE F E D C EXHAUST AIR INTAKE B Figure 10 Horizontal Snorkel Venting UNBALANCED VENTING WITH TEE INTAKE AND COUPLING EXHAUST All vent pipes must be glued properly su...

Страница 23: ...Concentric Vent Kit installation manual LP 166 for further information on venting with the optional concentric vent kits Concentric venting through an existing system must run vertically through the...

Страница 24: ...idered part of the space Confined space is space with volume less than 50 cubic feet per 1 000 Btu hour 4 8 cubic meters per kW of the total input rating of all fuel burning appliances installed in th...

Страница 25: ...rom 3 2 to 4 5 Install a neutralizing filter if required by local codes Power to the optional condensate pump is continuous When the water heater is powered off the condensate pump will remain on It i...

Страница 26: ...lp 441 Rev 002 Rel 008 Date 8 23 18 26 1 2 3 4 Figure 16 Removing and Installing the Condensate Neutralizer Water Heaters Manufactured Prior to 9 27 17 ONLY...

Страница 27: ...ns are included with the outdoor sensor to correctly mount the sensor on the exterior surface of the building It is preferable to mount the sensor on the north side in an area that will not be affecte...

Страница 28: ...ing plate LP for liquefied petroleum propane gas or Nat for natural or city gas All gas connections must be approved by the local gas supplier or utility in addition to the governing authority prior t...

Страница 29: ...being installed If there are additional gas appliances on the main supply line size the supply line for the maximum total COMBINED BTU Hr draw of the appliances This will ensure the supply line is siz...

Страница 30: ...s individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of the system at pressures greater than psi 3 5 kPa 2 The water heater must be isolated fr...

Страница 31: ...t in increments of two degrees After choosing the setpoint wait five seconds The screen will return to normal operation and the setpoint will be stored 70 160 120 Outdoor Reset Curve Enabling Outdoor...

Страница 32: ...ume water heater operation 3 Putting the Water Heater in ECO Mode Press to put the water heater in ECO Mode Press to resume normal operation 4 Changing User Setpoint Press either or once to change the...

Страница 33: ...mum tank temperature for reset curve 70 160 140 P10 Warm Weather Shutdown Temperature o C o F Outdoor temperatures greater than this value return the tank target temperature to the User Setpoint 50 10...

Страница 34: ...een cleared Press at any History Mode screens to return to the upper level menu Part 10 Start Up Procedure FOR YOUR OWN SAFETY READ BEFORE OPERATING 1 This water heater does not have a pilot It is equ...

Страница 35: ...maximum of 15 minutes 8 Test Mode can be disabled by pressing Combustion Settings on All Models Fan Speed Natural Gas NG Propane LP Low Ignition High Low Ignition High Carbon Monoxide CO PPM 1 10 2 1...

Страница 36: ...result in property damage serious personal injury or death Such damages ARE NOT covered by water heater warranty Part 12 Troubleshooting A Error Code An error code may occur during installation of the...

Страница 37: ...the sensor is 40o F 122o F 2 Check the Outdoor Temperature Sensor Ensure it is properly wired and connected and that there are no breaks cuts or other visible issues with the sensor wire 3 Use an ohmm...

Страница 38: ...ault code occurs again reset the water heater and 3 When water heater attempts to fire check voltage at the gas valve connector If there is voltage but no gas pressure on the outlet side of the valve...

Страница 39: ...erve water heater operation If fault code occurs again 3 Check the Dual Temperature Sensor Ensure it is properly wired to the control and that there are no breaks cuts or other visible issues with the...

Страница 40: ...ons been installed at least one foot above exterior grade and one foot above normal snow accumulation level Is vent piping properly supported Has vent piping been checked for leaks Has the exhaust ven...

Страница 41: ...er that has not been used for a long period of time generally two weeks or more When opening a hot water faucet in a system that has been out of use for a time keep all ignition sources electrical app...

Страница 42: ...ctrode Clean Set gap at 1 4 Clean probe with plumbers cloth to remove oxides Combination Ignitor and Flame Probe Check ionization in uA i04 in the Inquiry Mode menu Record high fire and low fire Clean...

Страница 43: ...T P A D A 4 8 6 0 P 0 0 7 7 S P M A L C w E S O H E T A S N E D N O C 5 4 4 0 P 0 0 1 7 B R A B X E L A M T P N 2 1 G N I T T I F 6 2 0 0 P 0 0 7 7 2 1 T U N K C O L 7 7 7 0 P 0 0 7 7 2 1 X 2 1 R E T...

Страница 44: ...0P 004 27 CONDENSATE HOSE w CLAMPS 7700P 068 28 FITTING 1 2 NPT MALE X BARB 7100P 044 29 LOCKNUT 1 2 7700P 002 30 ADAPTER 1 2 X 1 2 7700P 077 31 FLUE TEMPERATURE SENSOR 7450P 026 32 PRESSURE SWITCH 77...

Страница 45: ...of the water heater and NOT the date of installation of the water heater F This warranty extends only to water heaters utilized in water heating applications that have been properly installed by quali...

Страница 46: ...whenever possible d A picture of the piping near the product e For gas fired products a picture of the venting including how it exits the building All claims will be reviewed by HTP within three 3 bu...

Страница 47: ...lp 441 Rev 002 Rel 008 Date 8 23 18 47 Maintenance Notes...

Страница 48: ...allation Installation Address Product Name Serial Number s Comments Installer s Code Name Installers Phone Number Signed by Installer Signed by Customer Installation Notes IMPORTANT Customer Please on...

Отзывы: