DHW SETTINGS
CH/DHW Priority
>
Switch DHW-Prio
Time 30min
CH/DHW Priority sets the heating priority of the boiler.
The following options can be selected:
Time
- Priority changes after time.
CH-Prio
- Central heating always takes priority.
DHW-Prio
- Domestic hot water always takes priority.
Defaults is DHW-Prio, and 30 minutes. Range: 1 – 60 Minutes.
Table 39 – DHW Settings Quick Start-Up
Once the CH/DHW Priority is set, press
ENTER
to save. Press the
key to exit the Installer Menu return to the User Menu.
E. USER MENU BOILER SETTINGS
To view Boiler Settings: At the Main Screen, you can enter the User Menu by pressing the
key. At the initial User Menu screen, press
the
ENTER
key when the
>
icon is in line with Boiler Settings, and a series of Boiler Settings options can be accessed. These options
and corresponding screens are described below.
SCREEN
DESCRIPTION
BOILER SETTINGS
Central Heating
Setpoint
Outdoor Reset 180
o
F
In a cascaded system, “CH-Cascade” is shown. OutdoorReset is only shown when CH-mode 1 or
2 is used. This indicates that the setpoint cannot be changed. When not used, the installer can set
the setpoint for central heating.
Pressing the
▼ key allows the User to view more data.
BOILER SETTINGS
DHW-Store
Setpoint
119
o
F
Visible in DHW mode 1 and 2.
Displays the storage tank temperature setpoint if an indirect sensor is used.
The factory installed default setpoint is 119
o
F. Range: 104 – 160
o
F.
Table 40 – User Menu - Boiler Settings – Quick Start-Up
F. CASCADE FOLLOWER MAIN SCREENS
To view Cascade Follower Main Screens: Press the
key to return to the Main Menu
SCREEN
DESCRIPTION
BOILER ##
STANDBY: NO DEMAND
160°F
This display is visible at single and cascaded boilers. “BOILER ##” will only appear in cascaded
systems. ## stands for boiler address. Press
the ▼ key at the cascade master to view the outputs
of cascade followers. In this screen the boiler is in standby. There are no active outputs.
FPBSG BOILER ##
CENTRAL HEATING
100% 160°F
This screen displays operation status (modulation range and actual supply temperature) and active
outputs of the control. “BOILER ##” will only appear in cascaded systems. ## stands for boiler
address. Press
the ▼ key at the cascade master to view the outputs of cascade followers. Active
outputs of control are:
F
– Flame
P
- Pump for CH or general pump
B
– Blower
S
- Spark
G
- Gas valve
D
- DHW Pump or 3 WV
L
– Limited Modulation
Table 41 – Boiler Main Screens – Quick Start-Up
PART 14 – TROUBLESHOOTING
When servicing or replacing any components of this boiler, be certain that:
•
The gas is off.
•
All electrical power is disconnected.
When servicing or replacing components that are in direct contact with boiler water, be certain that:
•
There is no pressure in the boiler. (Pull the release on the relief valve. Do not depend on the pressure gauge reading.
•
The boiler water is not hot.
•
The electrical power is disconnected.
Содержание ELP-110
Страница 48: ...48 LP 294 REV 9 2 14 Figure 27 Single or Cascade Master and Cascade Follower Controls ...
Страница 49: ...49 LP 294 REV 9 2 14 Figure 28 ...
Страница 76: ...76 LP 294 REV 9 2 14 Figure 32 ...
Страница 77: ...77 LP 294 REV 9 2 14 Figure 33 LP 294 B ...
Страница 80: ...80 LP 294 REV 9 2 14 ...
Страница 81: ...81 LP 294 REV 9 2 14 ...
Страница 82: ...82 LP 294 REV 9 2 14 MAINTENANCE NOTES ...