G. Installer Mode
To activate Installer Mode, ensure the water heater display is powered off. Then press and hold button
for five seconds.
Figure 49 - Installer Mode Screens
Display
Default
Detail
Description
0:RC
Recirculation Pump
Operation
: Recirculation Pump is not used. (Recirculation and Preheat Modes are OFF.)
: Title 24 Mode (Required in California, Optional in other states). Recirculation
Mode requires a switch or motion sensor to activate.
: Preheat Mode is used. The water heater automatically turns on and meets the
DHW setpoint temperature when the internal temperature falls below the differential
setting (15:So).
: Internal Recirculation Mode - Internal Recirculation Pump is used.
: External Recirculation Mode - External Recirculation Pump is used.
1:EH
E0.00
Error history up to 10
Check ten most recent Error Codes (E0 - E9)
2:cE
OFF
Clear Error History
Select “ON” to Clear Error History. Range: ON or OFF
3:In
OFF
System Reset
(Factory Setting)
Select “ON” to restore system to default factory settings
(Burner operation time, Ignition cycles, and Supply power time will not be reset.)
Range: ON or OFF
4:FH
00
Maximum Fan Speed
Adjusts maximum fan speed. Range: -30 to +30
5:FL
00
Minimum Fan Speed
Adjusts minimum fan speed. Range: -30 to +30
6:dr
NO
Reset Burner Operation
Time
Select “YES” to Reset Burner Operation Time
Range: YES or NO
7:dl
NO
Reset Ignition Cycle
Select “YES” to Reset Ignition Cycles
Range: YES or NO
8:Cn
0
Cascade Address
Cascade Address
Range: 0 (Master), 1 (follower 1), …., 20 (follower 19). Default: 0.
NOTE:
“9:cP” needs to be set with total number of units in the cascade parameter before
setting “8: cn”
NOTE:
The Master water heater must always be addressed 0.
9:CP
1
Cascade Parameter
Number of Units Cascaded
Range: 01 - 20
10:CI
01
Minimum Operating
Number for Cascade
Units
Selects how many cascaded units will operate simultaneously when a DHW demand is
initially received.
Range: From 1 to Total Number of Units Cascaded
11:Eh
OFF
Factory Setting
Factory Setting - DO NOT CHANGE
12:Cr
Auto
Auto
Automatic Rotation
(default)
The first unit to operate when there is a DHW call is the unit that ran the least amount of
time during the prior heat calls (burner ON time).
Cr:Ct
48
Cascade Rotation Time
Cascade Rotation Time
NOTE:
If unit is set to run continuously, this parameter must be set, NOT Automatic Rota-
tion (Cr:at) to ensure even unit run time. Range: 0 - 240 Hours
13:HA
0-2
High Elevation Mode
This water heater may be installed at elevations up to 10,000 feet and operate on either
Natural or LP. The appliance will de-rate by 4% for each 1000 feet above sea level. Select the
appropriate installation location as described below.
Selects Installation Location for Proper Water Heater Operation at Altitude:
0-2 for installation locations from sea level to 1999 feet
2-5 for locations from 2000 to 4999 feet
5-8 for locations from 5000 to 7999 feet,
8-10 for locations from 8000 to 10000 feet
Default: 0 – 2
NOTE:
Use a combustion analyzer to ensure CO and CO2 are within the ranges shown in this
manual. Adjust the offset screw in the clockwise (positive) or counterclockwise (negative)
directions (approximately 1/8 turn) if the measured CO2 value on LOW FIRE is out of range.