lp-672 Rev. 000 Rel. 002 Date 10.3.18
41
F. Status Display
Status Display will activate when button
is pressed and held for five seconds at Standby Mode.
Figure 48 - Status Display Screen
Display
(Main Menu)
Display
(Sub Menu)
Detail
Description
A:GA or A:LI
Flow Unit
Current Flow Unit (LI: Liters/min, GA: Gallons/min)
b:dH
DHW outlet water temperature
Current DHW target temperature
C:In
DHW inlet water temperature
Current DHW inlet water temperature
d:Rt
Recirculation return water temperature
Current recirculation return water temperature
E:oP
Heat exchanger outlet water temperature
Current heat exchanger outlet water temperature
F:Eh
Exhaust temperature
Current exhaust temperature
H:oH
Overheat water temperature (HX)
Current overheat water temperature (HX)
I:Fr
Fan Speed (RPM)
Current Fan Speed (RPM)
L:rt
1:PH
Burner
Operation Time
Power supply
L:rt on display
on sub menu
Time water heater has been powered in 1000
hour units
2:rh
Burner operating time
Time burner has operated in 1 hour units
3:rH
Burner operating time
Time burner has operated in 1000 hour units
4:It
Ignition attempts
Number of ignition attempts: 10 times the
displayed unit
5:IH
Ignition attempts
Number of ignition attempts: 10,000 times
the displayed unit
M:CC
SELF
Capacity of Master (percentage)
N/A
ALL
Total Cascade Capacity (percentage)
N/A
F1 - F19
Capacity of individual water heaters
(percentage)
N/A
The following recirculation settings can be adjusted. See Using Recirculation Modes, Steps 1 and 2, this section, for further
details.
N:St
Auto
-
Default Recirculation Function
See Table 24 for more information.
NOTE:
Before setting the Recirculation Function, go into the
Installer Mode and change 0:RC from
or
to
(Internal Recirculation Mode) or
(External
Recirculation Mode). Recirculation Mode will not work if it is not
activated.
NOTE:
If
or
are selected, these settings cannot
be changed.
Pro1
4-9:30 AM,
4-7:30 PM
Recirculation Program 1
(preprogrammed or adjustable)
Pro2
6-7:30 AM,
6-7:30 PM
Recirculation Program 2
(preprogrammed or adjustable)
Pro3
-
Recirculation Program 3
(completely customized program)
PULS
10
Recirculation Pulse Function
O:tt
00
Optional Recirculation Temperature
Current recirculation temperature (using external pipe sensor)
when using Title 24 Mode. 00 will display when sensor is not
connected.
P:Lc
OFF
Lock Function
Turns Lock Function On and Off
Table 22 - Status Display Screen Descriptions
Turn the dial
counterclockwise and clockwise to scroll through the displayed parameters. To view parameter details, press the
button at the appropriate screen. Press the
or
buttons to leave the parameter.
Press the
button again to return to Operation Mode.