PQA400 - PQA823 - PQA824
EN - 111
In this page, the following symbols are used:
V1PE
Phase L1 - PE Voltage
V2PE
Phase L2 - PE Voltage
V3PE
Phase L3 - PE Voltage
V12
Phase L1 - Phase L2 Voltage
V23
Phase L2 - Phase L3 Voltage
V31
Phase L3 - Phase L1 Voltage
Inv%
% value of the Negative sequence unbalance
Omo%
% value of the Zero sequence unbalance
SEQ
Phase sequence:
”123” => Correct
”132” => Not correct
”023” => No Voltage on B1
”103” => No Voltage on B2
”120” => No Voltage on B3
”100” => No Voltage on B2 and B3
”020” => No Voltage on B1 and B3
”003” => No Voltage on B1 and B2
Hz
Frequency.
I1
Current on Phase L1
I2
Current on Phase L2
I3
Current on Phase L3
Fig. 184: Page 1/5 of numeric values for three-phase 3-wire system
The following keys are active on this page:
The
F1 key (or the PAG item on the display) advances to the following page of
saved values.
The
ESC key (or the smart icon on the display) to exit the function and go back
to the “Recording analysis” page (Fig. 143).
In this page, the following symbols are used:
Patt
System total Active Power
Preatt
Total Reactive Power
Papp
Total Apparent Power
Pf
Total Power Factor
CosPhi
System total CosPhi
CosPhi represents the theoretical limit value which
can be reached by the Power factor if all harmonics
are eliminated from the electrical system. For
dimensioning a power factor correction system,
reference is usually made to the CosPhi parameter
value.
Fig. 185: Page 2/5 of numeric values for three-phase 3-wire system
The following keys are active on this page:
The
F1 key (or the PAG item on the display) advances to the following page of
saved values.
The
ESC key (or the smart icon on the display) to exit the function and go back
to the “Recording analysis” page (Fig. 143).
Shop for HT products online at:
1.877.766.5412
www.
PowerMeterStore
.com