CAUTION
When starting test the unit performs a preliminary check of the resistance
values of current probe (Rc) and voltage probe (Rp) stopping the test if
these values are assumed to be too high and giving the messages “
Rc:
>2.0k
” and “
Rp: >2.0k
”. Decrease the resistance value wetting the
ground close to the probes and/or connect more probes in parallel
High noise currents and voltages in earth could affect the measurement
results. In this case the tester displays the ”NOISE” warning
6 Press
MEM
key to save the result inside memory (see § 8.1)
CAUTION
To view stored ground resistivity results on PC they must be downloaded to
the meter unit first. To download the results select earth results in Synchronize
menu (see § 5.1.3).
After the results are downloaded the stored data in
the station unit will be automatically deleted