HT2055
EN - 12
6 INITIAL OPERATIONS WITH HT2055S UNIT
Press the
or
function keys to display the below screens relative to the
earth/resistivity measurements and Settings (see Fig. 12)
Fig. 12: Screens of general menu
6.1 SETTINGS
The below operations are possible within Settings menu:
Language selection (see § 5.1.1)
Restore of default conditions
Setting power of current generator
Setting of alarm conditions when switching off test current
Recall at display of saved results (see § 8.2) and clear memory (see § 8.3)
Time/date setting (see § 5.1.5)
6.1.1 Default settings
This section permits to restore the default value (factory) of measurement parameters and
limits set on the instrument
Fig. 13: Initial settings screen
1. Press
or
keys to enter Settings menu
2. Select the item “Initial Settings” with the
or
keys and press
TEST
key
3. Select the “NO” or “YES” options with the
or
keys and confirm with
TEST
4. Press
ESC
key to exit and go back to the previous screen
The default values are the following:
Contrast
50%
Language
English
Alarm
Disabled
Power of generator
100%
Distance “a”
2.0m