9.2.1. Polarization Index (PI)
The purpose of this diagnostic test is to evaluate the influence of the polarization effects.
Upon the application of a high voltage to insulation, the electric dipoles distributed in the
insulation align in the direction of the applied electric field. This phenomenon is called
polarization. Because of the polarized molecules, a polarization (absorption) current
generates, which lowers the total value of insulation resistance.
Parameter
PI
consists in the ratio between the value of insulation resistance measured
after 1 minute and after 10 minutes. The test voltage is maintained throughout the whole
duration of the test and, at the end, the instrument provides the value of ratio:
min)
1
(
min)
10
(
Riso
Riso
PI
Some reference values:
PI Value
Insulation condition
from 1.0 to 1.25
Not acceptable
from 1.4 to 1.6
Good
>1.6 Excellent
9.2.2. Dielectric
Absorption Ratio (DAR)
Parameter
DAR
consists in the ratio between the value of insulation resistance measured
after 30s and after 1 minute. The test voltage is maintained throughout the whole duration
of the test and, at the end, the instrument provides the value of ratio:
)
30
(
min)
1
(
s
Riso
Riso
DAR
Some reference values:
DAR Value
Insulation condition
< 1.0
Dangerous
from 1.0 to 2.0 Questionable
from 2.0 to 4.0
Good
> 4.0
Excellent