EQUITEST
5071
EN - 15
Fig. 5: Instrument connection for LOW
10A test
5. Press the START key. The instrument starts testing.
CAUTION
When message "MEASURING…" is displayed, this indicates that the
instrument is carrying out the test. Never disconnect the instrument’s leads
during this phase.
At the end of the test, the
instrument gives out a
double sound to indicate
that test has been
correctly performed and
the following screen
appears on the display.
LOW
10A
31.11.12
0.107
13.4A
RLIM:0.100
Measured resistance
Test current
6. The displayed results can be saved by pressing the SAVE key twice (see § 7.1).