Silence buzzer: Icon is displayed when panel buzzer is manually silenced.
Silence alarm: Icon is displayes when active alarms are manually silenced.
5.4.
Working with main screen
HST-HP201-2 main screen is the default LCD screen that shows all fire & fault related
conditions information. Current system status is displayed at the left. By default, status is
normal which means that no fire or fault conditions are present at the panel.
First fire condition that panel detects after normal state is displayed at LCD and will not
be removed until fire reset is triggered. Its information is displayed on 2 lines. First line
contains name of the module which initiates the fire condition and its type. Second line
contains ID of the module, its loop in case of loop module (for onboard inputs, there is no
loop), its corresponding zone and date and time of initiation.
Note that after loop scan, default name which is given to loop device is ‘NODE XXX’.
XXX represents the ID of the device. So ‘NODE 009’ is the name of the loop device not it’s
ID. Name can be changed using programming menus.
After first fire field, there are 3 lines to show different fire, fault or manual evacuate
conditions based on which tab is highlighted at the bottom. You can switch between different
tabs with left and right arrows. If one list contains more than 3 conditions, you can show the
remaining records with up and down arrows.
List is ordered from the newest condition till the oldest condition. When new condition is
detected, its list will be updated and displayed at the top of its tab. If its tab is not the last
selected one, it will be selected automatically. For example, if new fire is detected and the last
selected tab is fault tab, fire tab will be selected and new fire will be displayed at the top. First
fire is not repeated in the fire tab window. For loop devices disconnected faults, if fault is
restored, its record will be removed from fault tab menu.