August-2015
Page 16
Normal state: This panel mode is valid as long as there is no fire or fault conditions
within the panel. In this mode, panel can detect any fire, manual evacuate or fault
conditions for all monitired modudes. LCD will write normal state message down to
date and time fields. Normal state is entered again after fire reset opearation..
Fire state: This panel mode is valid when any fire condition is detected. Panel will
change its LCD staus message to fire status down to date and time fields.
Evacuate state: This panel mode is valid when any manual evacuate condition is
detected. Panel will change its LCD staus message to evacuate status only if there is
no fire conditions in the panel. Fire conditions always override any fault or manual
evacuate conditions.
Fault state: This panel mode is valid when any fault is detected withing the panel.
Detected faults are: Loop faults, Loop devices faults, Power faults and onboard
sounder faults. Panel will change its LCD staus message to fault status only if there is
no fire or manual evacuate conditions in the panel. Fire conditions always override
any fault or manual evacuate conditions. Evacuate conditions always override any
fault conditions.
5.3.
LCD icons
HST-HP201-2 has 8 different LCD icons used to show some information about panel
operation. It is ordered from left to right of the screen.
Access level: It shows current panel access level. Access level 1 does not display any
icon.
Enable Key: Icon is displayed when Enable key is on.
Battery disconnected: Icon is displayed when backup batteries are not connected to
the panel.
Main power disconnected: Icon is displayed when panel is powered from backup
batteries. It is displayed on the same place of battery disconnected Icon (3
rd
icon).
Loop fault: Icon is displayed when any loop fault is deteced (open circuit, short
circuit, communication fault).
Sounder fault: Icon is displayed when any onboard sounder fault is deteced (open
circuit, short circuit).