NTG-3000 Operating Instructions Version 2.11
Page 8 of 18
8
Configuration
The transducer must be configured for the connected signals (terminal strips X500 to X503
and X600 to X602) before it is placed in operation for the first time. The 16-position rotary
switch labeled “
CONFIGURATION
” is used for configuration.
Note: The rotary switch is only evaluated during system startup
(when the supply voltage
is connected). Changes can be made to the settings of the rotary switch during operation but
these will have no impact on the system until the next startup.
8.1
Possible switch settings / configurations
The mode is selected using the 16-position rotary switch:
Currents:
DC signals
Mode
3-phase
(I1, I2, I3)
2-phase
(I1, I3)
Setting
1 A 5 A
0 to 20 m
A
4 to 20 m
A
0 X
X
2 (without debug data)
3-phase
1 X
X
2 (without debug data)
2
X
X
2 (without debug data)
3
X
X
2 (without debug data)
4 X
X
2+ (with debug data)
5 X
X
2+ (with debug data)
6
X
X
2+ (with debug data)
7
X
X
2+ (with debug data)
8 X
X
1
9 X
X
1
A
X
X
1
B
X
X
1
C X
X
2 (without debug data)
2-phase
D X
X
2 (without debug data)
E
X
X
2 (without debug data)
F
X
X
2 (without debug data)