HRW HPE8884BN V402 Manual 150622.docx E. & O. E. / Subject to change without notice
Page 9 of 23
Administration Commands
Function
Enter
Result
Options /
Comments
Start
communication
TTTTT(TTT…)
Display of configuration
and I/O status
With the Caps Lock on, hold the T key down
until the screen updates with HPE data. It is
not necessary to press the enter key to start
communication.
Download text
file
DE
Make ready for file path
Menu: Transfer > Send textfile >
file
Upload text file
UE
All settings are uploaded to
the terminal for archive or
re-use
HyperTerminal: Start a Capture Text
procedure before invoking UE then stop the
Capture after Upload complete.
Indigo you may simply copy the text on the
terminal screen to a text file.
Reset to
Factory Default
FD=1
Reset to ex-factory settings
FD will be displayed in the top line of the I/O
summary screen after reset
Set node
address (MAC)
98=1…98,
100…127,
128…247
Network node number is
assigned
Example: 98=25
1…98 / 100…127 the device will be a ‘token
passing master’
128… 247 the device will become a network
slave after power reset
Set system
Device Instance
DI=0…4194303
Unique Device Instance is
assigned
Example: DI=401025 (building 4, network 1,
node 25)
Set baud rate
99=…
Network comms speed is
set
2400, 4800,
9600
, 19200, 38400, 57600,
76800
Example: 99=9600
After Writing new comm. speed it will be
necessary to reconnect with Terminal at the
new comm. speed to continue the terminal
session!
Set Maximum
Master address
MM=1…127
Highest Master device
address on the network is
registered
Next address searching limited to MM
address
Set Sys.
Vendor ID
(
S
ys
V
id)
SV=0…255
System vendor specific
features may be available
SV=0 applies generic BACnet operation. If
an entered ID is not implemented then the
generic operation will be applied
Zero the Reset
counters
95=0, 96=0,
97=0
Each Reset counter is
zeroed
Factory diagnostics
Resets = <95> <96> <97>
Rx timeout, Tx timeout, Hardware reset
Write values as
default
W
Changes written.
Always do this after making changes that
you wish to be permanent
Exit
communication
X
Communication with
HyperTerminal no longer
active
Auto X after 240sec without key entry. After
eXit unplug the HPECOM cable to allow
network communication to take place