Chapter 6 Function Introduction
Shenzhen Hpmont Technology Co., Ltd.
―
58
―
HD3L Series Controller User Manual
Ref. Code
Function Description
Setting Range [Default]
F08.09
UP electrical torque limit
0.0 - 200.0 (F07.02) [180.0%]
F08.10
DN electrical torque limit
F08.11
UP regenerative torque limit
F08.12
DN regenerative torque limit
F08.09 - F08.12 are the relative percentage of motor rated
current (F07.02).
As the right figure:
•
The bigger torque output, the bigger current output.
•
If the torque is too big, over-current is easy to occur.
•
If the torque is too small, the run speed and the Acc /
Dec speed may deviate from the setting value.
6.2.10
F12: Digital I/O Terminal Parameters
Ref. Code
Function Description
Setting Range [Default]
F12.00
Input terminal filter time
0.000 - 1.000 [0.010s]
Defines filter time of digital input termianl and to set input terminal sensibility.
•
The input terminals are susceptible to interference which will result in misoperation, so F12.00 can be
increased. But too long filter time will affect sensibility.
F12.01 DI1
function
000 - 134 [1]
F12.02 DI2
function
000 - 134 [2]
F12.03 DI3
function
000 - 134 [3]
F12.04 DI4
function
000 - 134 [4]
F12.05 DI5
function
000 - 134 [5]
F12.06 DI6
function
000 - 134 [6]
F12.07
DI7 (I/O board) function
000 - 134 [0]
F12.08
DI8 (I/O board) function
000 - 134 [0]
F12.09
DI9 (I/O board) function
000 - 134 [0]
F12.10 Unused
F12.11 Unused
F12.12 Unused
Note: Hundred digit = 0, normally open input selected; = 1, normally closed input selected.
0: Unused. Terminal function is unused. HD3L ignores the signal input via this terminal.
•
The unused terminal is recommended to be set as 0 so as to avoid wrong connection or action.
1: Controller enabled (EN).
•
When enabled, HD3L is enabled to run.
•
When unused, HD3L is unused to run and will be in coasts to stop status.
•
When no terminal selects this function, it defaults that HD3L is at enabled status.
2,3: UP / DN.
•
Set control terminal to control up and down of elevator. The terminals are in below table.
UP (No. 2)
DN (No. 3)
Selection
0 0 Stop
0 1 Down
1 0 Up
1 1 Stop
123
Output torque
Motor Rpm
Up
Down
Positive
Negative
F08.10
F08.11
F08.12
F08.09