881629-001
2. Presentation
Description
Available settings
Default settings
In/Out settings
Load segments - Auto
shutdown delay
[Disable] [0 s] [1 s] [2 s]…[65354 s]
During a power outage,
authorizes UPS to turn off power to
equipment connected to Group 1
and/or Group 2 outlets.
This feature allows the shedding of
non-critical loads in order to conserve
battery power for critical loads
connected to the Primary Group.
Group 1: Disable
Group 2: Disable
Overload
prealarm
[10 %] [15 %] [20 %] ... [100 %] [105 %]
Sets critical percentage of load where
alarm overload alarm occurs.
[105 %]
ON/OFF settings
Cold start
[Disable] [Enable]
Enables the product to be started on
battery power.
First cold start is always disabled.
Enable
Forced reboot
[Disable] [Enable]
If AC power recovers during a
shutdown sequence:
- if enabled, shutdown sequence
completes and waits 10 seconds prior
to restart
- if disabled, shutdown sequence
does not complete and restart occurs
immediately.
Enable
Auto restart
[Disable] [Enable]
Enables the product to restart
automatically when AC power
recovers after a complete battery
discharge.
Enable
Energy saving
[Disable] [Enable]
If enabled, UPS shuts down after
5 minutes of backup time, if no load
is detected on the output.
Disable
Sleep mode
[Disable] [Enable]
If disabled, LCD and communication
turn OFF immediately after UPS is
OFF.
If enabled, LCD and communication
stay ON for 1.5 hours after UPS is
OFF.
Disable
Remote command
[Disable] [Enable]
If enabled, shutdown or restart
commands from software are
authorized.
Enable
RPO delay
[0 s] [1 s] [2 s]...[180 s]
Delays remote power OFF command.
[0 s]
Battery settings
Automatic battery test
[No test] [Every day] [Every week]
[Every month]
Available only if Battery Charge
mode is set to constant charge.
Every week
(in constant charge)
otherwise following
ABM
Low battery
warning
[1 %] [2 %] ... [100 %]
The alarm triggers when the set
percentage of battery capacity is
reached during a backup time.
20 %
Restart battery level
[1 %] [2 %] ... [100 %]
If set, automatic restart occurs only
when percentage of battery charge is
reached.
0 %
Battery charge mode
[ABM cycling] [Constant charge]
ABM cycling
Deep discharge protection [Yes] [No]
If set to Yes, the UPS automatically
prevents battery from deep discharge
by adapting end of backup time
voltage threshold.
Yes