1
Modular cabinet weight includes the PDUs and their associated wiring and receptacles.
2
Maximum payload weight for the 36U G2 rack cabinet: 1200 lbs (544.3 kg).
3
Maximum payload weight for the 42U G2 rack cabinet: 1200 lbs (544.3 kg).
4
Maximum payload weight for the 36U Intelligent rack cabinet: 3000 lbs (1360 kg).
5
Maximum payload weight for the 42U Intelligent rack cabinet: 3000 lbs (1360 kg).
6
iPDU=Intelligent PDU
7
mPDU=Modular PDU
For examples of calculating the weight for various enclosure combinations, see
Specifications for Enclosure Combinations” (page 71)
Modular Cabinet Stability
Cabinet stabilizers are required when you have less than four cabinets bayed together.
NOTE:
Cabinet stability is of special concern when equipment is routinely installed, removed,
or accessed within the cabinet. Stability is addressed through the use of leveling feet, baying
kits, fixed stabilizers, and/or ballast.
For information about the Intelligent rack, your Hewlett Packard Enterprise service provider can
consult the
HPE Intelligent Rack Family User Guide
.
NOTE:
For instructions on grounding the rack, ask your Hewlett Packard Enterprise service
provider to refer to the instructions in the
HPE Intelligent Rack Family Options Installation Guide
.
Environmental Specifications
This subsection provides information about environmental specifications and covers these topics:
•
“Heat Dissipation Specifications and Worksheet” (page 69)
•
“Operating Temperature, Humidity, and Altitude” (page 70)
•
“Nonoperating Temperature, Humidity, and Altitude” (page 71)
•
“Cooling Airflow Direction” (page 71)
•
“Typical Acoustic Noise Emissions” (page 71)
•
“Tested Electrostatic Immunity” (page 71)
Heat Dissipation Specifications and Worksheet
Total (BTU/hour)
Unit Heat
(BTU/hour)
Maximum
Unit Heat
(BTU/hour) Typical
Number Installed
Enclosure Type
1600
938
8 GB Blade element
1658
996
16 GB Blade element
1710
1037
32 GB Blade element
1112
894
VIO enclosure
768
461
DL380 G6 Storage
CLIM
682
444
DL380 G6 IP or Telco
CLIM
699
419
DL380p Gen8
Storage CLIM
Modular Cabinet Stability
69
Содержание Integrity NonStop NS2100
Страница 48: ...Figure 11 Modular PDU Connections Without UPS 48 System Installation Specifications for NS2100 Systems ...
Страница 49: ...Figure 12 Modular PDU Connections With Single Phase UPS Power Distribution for NS2100 Systems 49 ...
Страница 52: ...Figure 14 Example of Bottom AC Power Feed Without UPS 52 System Installation Specifications for NS2100 Systems ...
Страница 53: ...Figure 15 Example of Top AC Power Feed Without UPS Power Distribution for NS2100 Systems 53 ...
Страница 55: ...Figure 17 Example of Bottom AC Power Feed With Single Phase UPS Power Distribution for NS2100 Systems 55 ...
Страница 91: ...Figure 30 Example 36U Configuration Without UPS and ERM Typical NS2100 Configurations 91 ...
Страница 107: ...System Down OSM Low Level Link 107 ...