NonStop System with Cascading Rack-Mounted UPS and Data Center UPS
shows an example of a non-supported configuration in a NonStop system with the left
PDUs connected to the rack-mounted UPS, and the right PDUs connected to a data center UPS.
To create a cascading UPS configuration, the rack-mounted UPS is connected to the data center
UPS.
Figure 40 NonStop System With Cascading UPS
A cascading UPS configuration presents potential problems. Problems attaining stability between
the pair of cascaded UPSs can cause unexpected and undesirable behavior. The control loops
of each UPS can interfere with the other.
A typical scenario where this behavior occurs is the failure of the smaller downstream UPS to
recognize a stable input from its upstream source. In the event of an upstream UPS failure or
output disturbance, the downstream UPS switches the load to battery. Once the upstream UPS
regains full function, the downstream UPS should recognize a stable input and switch to
pass-through mode; but this does not happen in all cases and some cases fail.
In a failing case, the downstream UPS fails to switch back to pass-through mode, instead running
from the battery until the battery set is drained. Once the battery is drained, the downstream UPS
must attempt to switch back up to pass-through mode. At the minimum, this leaves the downstream
UPS with depleted batteries.
122
UPS and Data Center Power Configurations
Содержание Integrity NonStop NS2100
Страница 48: ...Figure 11 Modular PDU Connections Without UPS 48 System Installation Specifications for NS2100 Systems ...
Страница 49: ...Figure 12 Modular PDU Connections With Single Phase UPS Power Distribution for NS2100 Systems 49 ...
Страница 52: ...Figure 14 Example of Bottom AC Power Feed Without UPS 52 System Installation Specifications for NS2100 Systems ...
Страница 53: ...Figure 15 Example of Top AC Power Feed Without UPS Power Distribution for NS2100 Systems 53 ...
Страница 55: ...Figure 17 Example of Bottom AC Power Feed With Single Phase UPS Power Distribution for NS2100 Systems 55 ...
Страница 91: ...Figure 30 Example 36U Configuration Without UPS and ERM Typical NS2100 Configurations 91 ...
Страница 107: ...System Down OSM Low Level Link 107 ...