• Chassis with standard chassis controllers
◦ Chassis controllers to network (pink)
2.
Connect the chassis power supply cables (blue) to a PDU.
CAUTION:
The following illustration assumes that you are using one PDU per chassis that has a
minimum capacity of 17.28 kVA and a dedicated circuit breaker for each power supply in the chassis.
Connecting two or more power supplies to a single breaker will cause the breaker to trip. You might
need to add PDUs to your configuration to meet the requirement of one breaker per power supply to
avoid loss of data or damage to the PDU.