Specifications 24
UPS model
VA
Nominal power
rating (W)
Nominal voltage
setting
T750 INTL
750
500
220, 230, 240
Voltage specifications
Configuration setting (VAC)
Available nominal output voltage (VAC)
100 100
110 110
120 120
220 220
230 230
240 240
Output tolerance specifications
Source of power
Regulation
Utility power (nominal
range)
-10% to +6% of nominal output voltage rating
(within the guidelines of the Computer Business
Equipment Manufacturers Association)
Battery power
±10% of nominal output voltage rating
Output feature specifications
Feature Specification
Online efficiency
94% nominal input voltage
Voltage wave shape
Sine wave; 5% THD with typical PFC load
Surge suppression
High-energy 6500 A peak
Noise filtering
MOVs and line filter for normal and common mode
use
Battery specifications
Feature Specification
Type
Each model contains maintenance-free, sealed, valve regulated
lead-acid batteries with a 3-year minimum float service life at
25°C (77°F).
Voltage
The battery modules have a battery string voltage of 24 V.
Charging
Complete charge takes no more than 24 hours. After
approximately 4 hours, the batteries reach 90% charge at
default nominal utility voltage and no load.
Содержание T750
Страница 1: ...HP UPS T750 User Guide March 2006 Third Edition Part Number 382249 003 ...
Страница 17: ...UPS operations 17 4 Wait at least 60 seconds for the UPS internal circuitry to discharge ...
Страница 29: ...Warranty information 29 Notification from power management software ...
Страница 33: ...Regulatory compliance notices 33 Japanese notice BSMI notice Korean notice Class A equipment Class B equipment ...