background image

Audible Noise

<46db (at 1m from surface of unit)

Safety Markings

NA/JPN: UL, cUL
Int'l: GS, CE, GOST

Safety Certifications

UL1778, UL60950-1; CSA22.2 No.107.3, No.60-1950; EN50091-1-1;
EN60950-1 IEC62040-1-1

EMC Markings

NA/JPN: FCC, VCCI, ICES, CISPR
Int'l: BSMI, C-Tick, CISPR

Emissions

FCC CFR 47, Part 15 Class A, EN50091-2

Immunity

IEC 801-2, IEC 801-3, IEC 801-4, IEC 801-5

REPO Port

Meets NEC code 645-11 intent and UL requirements

Environment-friendly
Products and Approach

End-of-life Management
and Recycling

Hewlett-Packard offers end-of-life HP product return, trade-in, and recycling
programs in many geographic areas. For trade-in information, please go to:

http://www.hp.com/go/green

. To recycle your product, please go to:

http://www.hp.com/go/green

 or contact your nearest HP sales office.

Products returned to HP will be recycled, recovered or disposed of in a
responsible manner.

The EU WEEE directive (2002/95/EC) requires manufacturers to provide
treatment information for each product type for use by treatment facilities.
This information (product disassembly instructions) is posted on the Hewlett
Packard web site at: 

http://www.hp.com/go/green

. These instructions may be

used by recyclers and other WEEE treatment facilities as well as HP OEM
customers who integrate and re-sell HP equipment.

© Copyright 2013 Hewlett-Packard Development Company, L.P.
The information contained herein is subject to change without notice.

The only warranties for HP products and services are set forth in the express warranty statements accompanying such products and
services. Nothing herein should be construed as constituting an additional warranty. HP shall not be liable for technical or editorial
errors or omissions contained herein.

QuickSpecs

R7000 Uninterruptible Power System (UPS)

Technical Specifications

DA - 14110   North America — Version 5 — August 23, 2013

Page  11

Содержание R7000 INTL

Страница 1: ...cks and cost conscious co located data center applications Front View Rear View 1 Escape Button 1 Load segment 1 circuit breaker controls L6 30R receptacle Item 3 2 Scroll up button 2 Load segment 2 circuit breaker controls L6 30R receptacle Item 15 3 Scroll down button 3 Large output NEMA L6 30R receptacle or IEC 60309 32A receptacle on short cords associated with load segment 1 4 Enter Select bu...

Страница 2: ...er on the sales order if HP factory integration is indicated HP R7KVA 4U 50A High Voltage Uninterruptible Power System AF462A Kit Contents HP UPS R7000 HP UPS Network Module Power Products Documentation CD Depth adjustable fixed rack mounting rails mounting brackets cord retention clips Communications cable Two 7xC13 Extension Bars QuickSpecs R7000 Uninterruptible Power System UPS Overview DA 1411...

Страница 3: ...ology The HP UPS R7000 utilizes a the Digital Signal Processing industry leading technology that continually conditions and regulates power without using the battery thereby increasing the life of the battery The output voltage is automatically regulated based on the connected load and the input voltage Investment Protection with HP Enhanced Battery Management HP UPS R7000 incorporates Enhanced Ba...

Страница 4: ...product improvement and an unsurpassed warranty guarantee the highest level of system protection electrical performance product quality and compatibility Compatibility Compatible with all HP servers storage racks rack options and other rack mountable HP equipment For PDU options please refer to the UPS PDU compatibility matrix on www hp com products ups Warranty The HP UPS R7000 is covered by a th...

Страница 5: ...ve Select Service Credits when you purchase your hardware and then use the credits over the next 12 months http h20195 www2 hp com V2 GetPDF aspx 4AA2 3842ENN Insight Remote Support Delivers secure remote monitoring and support for HP servers and storage 24x7 at no additional cost Available as part of HP Warranty Care Pack and Service Contract offers Parts and materials HP will provide HP supporte...

Страница 6: ...on To learn more on services for HP ESSN Options please contact your HP sales representative or HP Authorized Channel Partner Or visit http www hp com services proliant or www hp com services bladesystem QuickSpecs R7000 Uninterruptible Power System UPS Service and Support DA 14110 North America Version 5 August 23 2013 Page 6 ...

Страница 7: ...ter the part number on the sales order if HP factory integration is indicated AF464A HP Care Pack HP Install Universal Power Supply 3KVA to Below 6KVA Service U4693E QuickSpecs R7000 Uninterruptible Power System UPS Related Options DA 14110 North America Version 5 August 23 2013 Page 7 ...

Страница 8: ...Connection Output Connection AF462A 200 208 7200VA 7200W Hubble CS8265C 3m cord LS1 15A CB 3 x C19 1 x L6 30R LS2 15A CB 3 x C19 1 x L6 30R Factory default setting QuickSpecs R7000 Uninterruptible Power System UPS UPS Model Matrix DA 14110 North America Version 5 August 23 2013 Page 8 ...

Страница 9: ... Modules Minutes 20 52 98 301 50 13 33 103 80 6 18 57 100 4 13 39 NOTE Backup times are estimated for typical applications Actual performance will depend on load and battery conditions QuickSpecs R7000 Uninterruptible Power System UPS Estimated Backup Times Chart Minutes DA 14110 North America Version 5 August 23 2013 Page 9 ...

Страница 10: ... supported Backup Time See Backup Times Chart Recharge Time 3 hours to 80 usable capacity 48 hours for complete recharge Battery String Voltage 216V Battery Type 12V 45W Battery Quantity 18 Maximum wattage based on voltage input AF426A 200 240V 7200VA 7200W Communications Serial Ports Standard DB 9 ports ships with communication cable Included HP UPS Network Module LED Indicators LED and switch me...

Страница 11: ...recovered or disposed of in a responsible manner The EU WEEE directive 2002 95 EC requires manufacturers to provide treatment information for each product type for use by treatment facilities This information product disassembly instructions is posted on the Hewlett Packard web site at http www hp com go green These instructions may be used by recyclers and other WEEE treatment facilities as well ...

Отзывы: