UPS operations
Mimic screen
The Mimic screen shows the internal components of the UPS and a real-time display of the operating status.
A thicker bar indicates that the node is energized.
Modes of operation
The UPS has four modes of operation:
•
Standby mode (on page
64
)
•
Normal mode (on page
65
)
•
Battery mode (on page
66
)
•
Auto-Bypass mode (on page
66
)
Standby mode
In Standby mode:
•
No power is available at the UPS output receptacles.
•
The UPS charges the batteries as necessary.
The UPS can be placed in Standby mode when the UPS is in Normal mode (on page
65
).
To place the UPS in Standby mode:
1.
Power down the UPS.