System Unit
Dimensions
(H x W x D)
(with bezel)
3.45" x 17.64" x 28.23" in (8.76 x 44.80 x 71.71 cm)
Weight
(approximate)
Maximum
(all hard drives, power
supplies, and processors
installed)
45.0 lb (16.80 kg)
Minimum
(one hard drive, power
supply, and processor
installed)
32.0 lb (11.94 kg)
Input Requirements
(per power supply)
Rated Line Voltage
90 -- 132 VAC,
180 - 264 V
Rated Input Current
460 Watt
7.1 A (at 120 VAC)
3.5 A (at 240 VAC)
750 Watt
7.4 A (at 120 VAC)
3.6 A (at 240 VAC)
Rated Input Frequency
50 to 60 Hz
Rated Input Power
460 & 750 watt - 852 W
BTU Rating
Maximum
460 Watt
1773 BTU/hr (at 120
VAC)
1715 BTU/hr (at 240
VAC)
750 Watts
2892 BTU/hr (at 120
VAC)
2797 BTU/hr (at 240
VAC
Power Specifications
To review typical system power ratings use the Power Advisor which is
available via the online tool located at URL:
www.hp.com/go/proliant-energy-
efficient
Click on the system of interest. Example: DL180 G6
Follow the instructions of the next screens.
Power Supply Output
(per power supply)
Rated Steady-State
Power
460 W (at 100 VAC)
750 W (at 100 VAC)
460 W (at 200 VAC)
750 W (at 200 VAC)
Maximum Peak Power
460 W (at 100 VAC)
750 W (at 100 VAC)
460 W (at 200 VAC)
750 W (at 200 VAC)
System Inlet
Temperature
Operating
10° to 35°C (50° to 95°F) at sea level with an
altitude derating of 1.0°C per every 305 m (1.8°F
per every 1000 ft) above sea level to a maximum
of 3050 m (10,000 ft), no direct sustained
sunlight. Maximum rate of change is 10°C/hr
(18°F/hr). The upper limit may be limited by the
type and number of options installed.
QuickSpecs