3 NS7 System Installation Specifications
This chapter provides specifications necessary for system installation planning. All specifications
in this chapter assume that each enclosure in the rack is fully populated. The maximum current
for each AC service depends on the number and type of enclosures installed in the rack. Power,
weight, and heat loads are less when enclosures are not fully populated; for example, a SAS
disk enclosure with fewer disks.
Racks
The rack is an EIA standard 19-inch , 36U or 42U rack. The rack comes equipped with front and
rear doors and includes a rear extension that makes it deeper than some industry-standard racks.
The PDUs described in
“Power Distribution Unit (PDU) Types for a Rack ” (page 24)
are mounted
along the rear extension without occupying any U-space in the rack and are oriented inward,
facing the components within the rack.
NOTE:
For instructions on grounding the Enterprise series rack (formerly known as the Intelligent
rack) using the HPE Rack Ground Bonding Kit (BW891A), ask your service provider to see the
instructions in the:
•
HP Rack Options Installation Guide
•
http://www.hpe.com/support/Intelligent_Series_Rack_Manuals
Power Distribution Unit (PDU) Types for a Rack
The Enterprise series rack (formerly known as the Intelligent rack) supports Intelligent PDUs
(iPDUs) and Modular PDUs. Both PDU types use a core and extension bar design with these
characteristics:
•
PDU cores power the extension bars and c7000 enclosure.
•
PDU cores are mounted at the lowest possible U location in the rack. Two PDUs are mounted
in the same U location (rear and front).
•
Extension bars are mounted on the rear vertical rails of the rack.
•
Rear-mounted PDU cores connect to the extension bars on the right side of the rack.
•
Front-mounted PDU cores connect to the extension bars on the left side of the rack.
•
If the rack is equipped with a UPS, the UPS outputs connect to the front-mounted PDU
cores.
NOTE:
A rack with a c7000 enclosure requires a four PDU core configuration. Racks without
a c7000 enclosure use a two PDU core configuration.
24
NS7 System Installation Specifications
Содержание Integrity NonStop X NS7
Страница 8: ...Figure 1 Example NS7 System Configurations 42U and 36U 8 HPE Integrity NonStop X NS7 Systems ...
Страница 39: ...Figure 14 Example of Bottom AC Power Feed in a Rack Without UPS AC Power Feeds in the Rack 39 ...
Страница 40: ...Figure 15 Example of Top AC Power Feed in a Rack Without UPS 40 NS7 System Installation Specifications ...
Страница 41: ...Figure 16 Example of Top AC Power Feed in a Rack With Single Phase UPS AC Power Feeds in the Rack 41 ...
Страница 43: ...Figure 18 Example of Top AC Power Feed in a Rack With Three Phase UPS AC Power Feeds in the Rack 43 ...
Страница 62: ...62 HPE Integrity NonStop X NS7 CG X2 System ...