![HP Integrity MC990 X Скачать руководство пользователя страница 59](http://html.mh-extra.com/html/hp/integrity-mc990-x/integrity-mc990-x_user-manual_164437059.webp)
Feature
Specification
Relative humidity
20% to 80% operating (no condensation)
8% to 80% non-operating (no condensation)
Heat dissipation to air
Approximately 17.74 kBTU/hr (1.48 tons)
Cooling requirement
Ambient air cooling
Single chassis air-flow: intake (front),
exhaust (rear)
650 CFM Max (1104 m3/hr)
475 CFM typical (407 m3/hr)
Maximum altitude
10,000 ft. (3,049 m) operating
40,000 ft. (12,195 m) non-operating
Acoustic sound pressure
Approximately 77 dBA (at rear of rack)
Integrity MC990 X system electrical specifications
MC990 X system electrical specifications
shows the power specifications for the MC990 X system.
Table 7: MC990 X system electrical specifications
Feature
Specification
Server chassis power supply (4 per chassis)
12-Volt, 1600 Watt (Platinum) [200-240 VAC]
12-Volt, 1000 Watt (Platinum) [100-120 VAC]
Server chassis power cords
Four 8-ft (2.4 m) drop cables
Server chassis power requirements
Voltage
100-120V (90-140 VAC min/max)
200-240V (180-264 VAC min/max)
Frequency
50-60 Hz (47-63 Hz min/max)
Power (maximum per MC990 X server chassis)
5.33 kVA (5.22kW) per chassis
Hold-up time
10 ms
Single-phase PDU power requirements
Voltage
180-264 VAC
Frequency
50-60 Hz
Three-phase PDU power requirements
Table Continued
Integrity MC990 X system electrical specifications
59