Removal and replacement procedures 65
10.
Install the heatsink.
IMPORTANT:
Install all components with the same configuration that was used on the failed
system board.
11.
Install all components removed from the failed system board.
12.
Install the access panel.
13.
Install the power supplies ("
14.
Power up the server.
After you replace the system board, you must re-enter the server serial number and the product ID.
1.
During the server startup sequence, press the
F9
key to access UEFI System Utilities.
2.
Select the
System Configuration
>
BIOS/Platform Configuration (RBSU)
>
Advanced Options
>
Advanced System ROM Options
>
Serial Number
, and then press the
Enter
key.
3.
Enter the serial number and press the
Enter
key. The following message appears:
The serial number should only be modified by qualified service personnel.
This value should always match the serial number located on the chassis.
4.
Press the
Enter
key to clear the warning.
5.
Enter the serial number and press the
Enter
key.
6.
Select
Product ID
. The following warning appears:
Warning: The Product ID should ONLY be modified by qualified service
personnel. This value should always match the Product ID located on the
chassis.
7.
Enter the product ID and press the
Enter
key.
8.
Press the
F10
key to confirm exiting System Utilities. The server automatically reboots.
HP Trusted Platform Module
The TPM is not a customer-removable part.
CAUTION:
Any attempt to remove an installed TPM from the system board breaks or
disfigures the TPM security rivet. Upon locating a broken or disfigured rivet on an installed
TPM, administrators should consider the system compromised and take appropriate measures
to ensure the integrity of the system data.