©  2019  Hoymiles  Converter  Technology  Co.,  Ltd.  All  rights  reserved.

                                            17   

 

HME-1000T/1200T/1350T/1500T-AU 

 

208 

Input port 3 & 4 

undervoltage

 

1.Please make sure that the PV module open-circuit voltage is less than 

or equal to the maximum input voltage. 

2.  If  the  PV  module  open-circuit  voltage  is  within  the  normal  range, 

contact your dealer or Hoymiles technical support.

 

209 

Port1 No input

 

1. Please confirm whether this port is connected to the PV module; 

2. If the PV module is connected, please check the DC cable connection 

between this port and the PV module.

 

210 

Port 2 No input

 

1. Please confirm whether this port is connected to the PV module; 

2. If the PV module is connected, please check the DC cable connection 

between this port and the PV module.

 

211 

Port 3 No input 

1. Please confirm whether this port is connected to the PV module; 

2. If the PV module is connected, please check the DC cable connection 

between this port and the PV module. 

212 

Port 4 No input 

1. Please confirm whether this port is connected to the PV module; 

2. If the PV module is connected, please check the DC cable connection 

between this port and the PV module. 

213 

PV-1 & PV-2 

abnormal wiring 

Please check whether the DC connections on port 1 and 2 are correct. 

214 

PV-3 & PV-4 

abnormal wiring 

Please check whether the DC connections on port 3 and 4 are correct. 

301 

Hardware Error Code 

301

 

1.  If  the  alarm  occurs  accidentally  and  the  microinverter  can  still  work 

normally, no special treatment is required. 

2. If the alarm occurs frequently and cannot be recovered, contact your 

dealer or Hoymiles technical support.

 

302 

Hardware Error Code 

302

 

1.  If  the  alarm  occurs  accidentally  and  the  microinverter  can  still  work 

normally, no special treatment is required. 

2. If the alarm occurs frequently and cannot be recovered, contact your 

dealer or Hoymiles technical support.

 

303 

Hardware Error Code 

303

 

1.  If  the  alarm  occurs  accidentally  and  the  microinverter  can  still  work 

normally, no special treatment is required. 

2. If the alarm occurs frequently and cannot be recovered, contact your 

dealer or Hoymiles technical support.

 

304 

Hardware Error Code 

304

 

1.  If  the  alarm  occurs  accidentally  and  the  microinverter  can  still  work 

normally, no special treatment is required. 

2. If the alarm occurs frequently and cannot be recovered, contact your 

dealer or Hoymiles technical support.

 

305 

Hardware Error Code 

305

 

1.  If  the  alarm  occurs  accidentally  and  the  microinverter  can  still  work 

normally, no special treatment is required. 

2. If the alarm occurs frequently and cannot be recovered, contact your 

dealer or Hoymiles technical support.

 

306 

Hardware Error Code 

306

 

1.  If  the  alarm  occurs  accidentally  and  the  microinverter  can  still  work 

normally, no special treatment is required. 

2. If the alarm occurs frequently and cannot be recovered, contact your 

dealer or Hoymiles technical support.

 

Содержание HME-1000T-AU

Страница 1: ...Version 1 2 June 2020...

Страница 2: ...control the production of a single photovoltaic module directly consequently improving the flexibility and reliability of the system About the Manual This manual contains important instructions for t...

Страница 3: ...hlights 8 3 3 Terminals Introduction 8 3 4 Dimension mm 8 4 About Function 9 4 1 Work Mode 9 5 About Installation 9 5 1 Accessories 9 5 2 Installation Precaution 10 5 3 Space Distance Required 10 5 4...

Страница 4: ...ification 22 8 2 Power Quality Response Modes 22 8 3 DRM 22 9 Technical Data 23 8 1 DC Input 23 8 2 AC Output 23 8 3 Efficiency Safety and Protection 24 8 4 Mechanical Data 24 8 5 Features 24 Appendix...

Страница 5: ...below 2 About Safety 2 1 Important Safety Instructions The HME 1000T 1200T 1350T 1500T AU Microinverter is designed and tested according to international safety requirements However certain safety pr...

Страница 6: ...onal protective equipment including gloves and eye protection during the installation Inform the manufacturer about non standard installation conditions Do not use the equipment if any operating anoma...

Страница 7: ...at the interference will not occur in a particular installation To confirm that the radio or television reception is interfered by this equipment you can turn the equipment off and on If this equipmen...

Страница 8: ...efficiency 96 70 CEC weighted efficiency 96 50 Static MPPT efficiency 99 80 Dynamic MPPT efficiency 99 76 in overcast weather Power factor adjustable 0 8 leading 0 8 lagging External antenna for stron...

Страница 9: ...Grid Stand by There are several circumstance that Microinverter will stay in Standby mode The current condition is contradicted with Microinverter operating requirement No house loads or the Export co...

Страница 10: ...sure to ensure ventilation and heat dissipation Note For some countries the DTU will be required to meet the local grid regulation e g G98 99 for UK etc 5 3 Space Distance Required If the microinverte...

Страница 11: ...rating due to an increase in the microinverter internal temperature do not expose it to direct sunlight To avoid overheating always make sure the air flow around the inverter is not blocked Do not in...

Страница 12: ...se install the microinverter at least 50cm above the ground roof for better communication with Hoymiles DTU Step 2 Complete the AC Connection A Attach the AC bus cable with the mounting rail and fix t...

Страница 13: ...slot accordingly Tighten the screws and then tighten the cap back to the port Plug the upper cover back to the bus connector B Connect the other side of the AC end cable to the distribution box and w...

Страница 14: ...install the DTU and set up the monitoring system Product information is subject to change without notice Please download reference manuals at www hoymiles com 6 Troubleshooting 6 1 Troubleshooting Li...

Страница 15: ...ween the DTU and the microinverter If the communication is poor try to make some improvements 3 If the alarm occurs frequently and cannot be recovered contact your dealer or Hoymiles technical support...

Страница 16: ...rid frequency change rate is within the acceptable range If no contact the local power operator or change the grid frequency change rate limit via Hoymiles monitoring system with the consent of the lo...

Страница 17: ...correct 301 Hardware Error Code 301 1 If the alarm occurs accidentally and the microinverter can still work normally no special treatment is required 2 If the alarm occurs frequently and cannot be re...

Страница 18: ...Flashing green five times 0 3s gap Start up success Flashing Red five times 0 3s gap Start up failure 2 Run Process Flashing Fast Green 1s gap Producing power Flashing Slow Green 2s gap Producing powe...

Страница 19: ...lease return it to the factory for replacement 6 4 Routine Maintenance 1 Only authorized personnel are allowed to carry out the maintenance operations and are responsible to report any anomalies 2 Alw...

Страница 20: ...unit 6 5 Replace Microinverter a How to remove the Microinverter De energize the AC branch circuit breaker Remove the PV panel from the racking and cover the panel Using a meter to measure and make s...

Страница 21: ...particular the electronic components from violent shocks humidity vibration etc Please dispose the packaging elements in appropriate ways to avoid unforeseen injury It is the customer s responsibilit...

Страница 22: ...ting the PV System to Hoymiles monitoring app portal For details of how to configure monitoring please refer to document HMP Operating Guide Webpage V2 0 and HMP Operation Guide APP 8 2 Power Quality...

Страница 23: ...rter Refer to Hoymiles Warranty Terms Conditions for more information 8 1 DC Input 8 2 AC Output Model HME 1000T AU HME 1200T AU HME 1350T AU HME 1500T AU Commonly used module power W Up to 310 single...

Страница 24: ...verter efficiency 96 70 96 70 96 70 96 70 CEC weighted efficiency 96 50 96 50 96 50 96 50 Nominal MPPT efficiency 99 80 99 80 99 80 99 80 Night time power consumption mW 50 50 50 50 Model HME 1000T AU...

Страница 25: ...2019 Hoymiles Converter Technology Co Ltd All rights reserved 25 HME 1000T 1200T 1350T 1500T AU...

Страница 26: ...2019 Hoymiles Converter Technology Co Ltd All rights reserved 26 HME 1000T 1200T 1350T 1500T AU Appendix 1 Installation Map...

Страница 27: ...RING DIAGRAM 230VAC SINGLE PHASE GROUND NEUTRAL W AC DISTRIBUTION PANEL OR SUBPANEL METER AC BRANCH CABLE BROWN L BLUE N YELLOW GREEN G L1 PHASE L1 ETHERNET CONNECTION TO BROADBAND ROUTER CONNECTION T...

Страница 28: ...IBUTION PANEL OR SUBPANEL METER AC BRANCH CABLE BROWN L BLUE N YELLOW GREEN G L1 L2 L3 ETHERNET CONNECTION TO BROADBAND ROUTER CONNECTION TO DTU POWER ADAPATER 5V DTU UP TO 24 HME 1500T AUs PHASE L1 P...

Отзывы: