Heating system control
Function
Mode displa
y
P
ar
ameter
Displa
y
V
alue displa
y
Meaning, description
Inf
ormation mode
Here, you can read
out current
values
Dot flashes
0
e.g. 45°
Current flow temperature (heating water temperature)
1
e.g. 40°
Current return temperature
2
e.g. 60°
Current temperature in the calorifier
3
e.g. 3°
Current outside temperature
4
e.g. 55°
Current flue gas temperature
5
e.g. 50°
Set flow value in heating operation
6
e.g. 70°
Set flow value in DHW operation
7
e.g.23 rpm
Fan speed in hundred rpm
8
e.g. 4 µ A
Ionisation current
P
arameter mode
Settings can be changed in this mode.
Dot appears
P. 7
60
= DHW reference value
if no TopTronic
®
connected
Proceed as follows:
P. 18
80
= Max. flow temperature in heating operation
1. Select Parameter mode
(Press mode key twice).
The parameter (P.7) and the setting
value are displayed alternately.
Par. 18
2. Select the parameter to be changed
(Step key)
3. Change the setting using
+ - keys
4. Save
(Press Store key once)
Return to Standby mode automati-
cally after 20 minutes or by pressing
Mode key.
Further parameters only with service code